Matching Items (59)
Filtering by

Clear all filters

149510-Thumbnail Image.png
Description
Optical Instrument Transformers (OIT) have been developed as an alternative to traditional instrument transformers (IT). The question "Can optical instrument transformers substitute for the traditional transformers?" is the main motivation of this study. Finding the answer for this question and developing complete models are the contributions of this work. Dedicated

Optical Instrument Transformers (OIT) have been developed as an alternative to traditional instrument transformers (IT). The question "Can optical instrument transformers substitute for the traditional transformers?" is the main motivation of this study. Finding the answer for this question and developing complete models are the contributions of this work. Dedicated test facilities are developed so that the steady state and transient performances of analog outputs of a magnetic current transformer (CT) and a magnetic voltage transformer (VT) are compared with that of an optical current transformer (OCT) and an optical voltage transformer (OVT) respectively. Frequency response characteristics of OIT outputs are obtained. Comparison results show that OITs have a specified accuracy of 0.3% in all cases. They are linear, and DC offset does not saturate the systems. The OIT output signal has a 40~60 μs time delay, but this is typically less than the equivalent phase difference permitted by the IEEE and IEC standards for protection applications. Analog outputs have significantly higher bandwidths (adjustable to 20 to 40 kHz) than the IT. The digital output signal bandwidth (2.4 kHz) of an OCT is significantly lower than the analog signal bandwidth (20 kHz) due to the sampling rates involved. The OIT analog outputs may have significant white noise of 6%, but the white noise does not affect accuracy or protection performance. Temperatures up to 50oC do not adversely affect the performance of the OITs. Three types of models are developed for analog outputs: analog, digital, and complete models. Well-known mathematical methods, such as network synthesis and Jones calculus methods are applied. The developed models are compared with experiment results and are verified with simulation programs. Results show less than 1.5% for OCT and 2% for OVT difference and that the developed models can be used for power system simulations and the method used for the development can be used to develop models for all other brands of optical systems. The communication and data transfer between the all-digital protection systems is investigated by developing a test facility for all digital protection systems. Test results show that different manufacturers' relays and transformers based on the IEC standard can serve the power system successfully.
ContributorsKucuksari, Sadik (Author) / Karady, George G. (Thesis advisor) / Heydt, Gerald T (Committee member) / Holbert, Keith E. (Committee member) / Ayyanar, Raja (Committee member) / Farmer, Richard (Committee member) / Arizona State University (Publisher)
Created2010
149405-Thumbnail Image.png
Description
The U.S. Navy is interested in evaluating the dielectric performance of SF6 at 30 kHz in order to develop optimal bushing designs and to ensure reliable operation for the Very Low Frequency/ Low Frequency (VLF/LF) transmitting stations. The breakdown experiments of compressed SF6 at 30 kHz in the pressure range

The U.S. Navy is interested in evaluating the dielectric performance of SF6 at 30 kHz in order to develop optimal bushing designs and to ensure reliable operation for the Very Low Frequency/ Low Frequency (VLF/LF) transmitting stations. The breakdown experiments of compressed SF6 at 30 kHz in the pressure range of 1-5 atm were conducted in both the uniform field (plane-plane gap) and the non-uniform field (rod-plane gap). To understand the impact of pressure on the breakdown voltage of SF6 at VLF/LF, empirical models of the dielectric strength of SF6 were derived based on the experimental data and regression analysis. The pressure correction factors that present the correlation between the breakdown voltage of SF6 at VLF/LF and that of air at 50/60 Hz were calculated. These empirical models provide an effective way to use the extensively documented breakdown voltage data of air at 60 Hz to evaluate the dielectric performance of SF6 for the design of VLF/LF high voltage equipment. In addition, several breakdown experiments and similar regression analysis of air at 30 kHz were conducted as well. A ratio of the breakdown voltage of SF6 to that of air at VLF/LF was calculated, from which a significant difference between the uniform gap and the non-uniform gap was observed. All the models and values provide useful information to evaluate and predict the performance of the bushings in practice.
ContributorsHan, Jian (Author) / Gorur, Ravi S (Thesis advisor) / Farmer, Richard G (Committee member) / Karady, George G. (Committee member) / Arizona State University (Publisher)
Created2010
156785-Thumbnail Image.png
Description
The students of Arizona State University, under the mentorship of Dr George Karady, have been collaborating with Salt River Project (SRP), a major power utility in the state of Arizona, trying to study and optimize a battery-supported grid-tied rooftop Photovoltaic (PV) system, sold by a commercial vendor. SRP believes this

The students of Arizona State University, under the mentorship of Dr George Karady, have been collaborating with Salt River Project (SRP), a major power utility in the state of Arizona, trying to study and optimize a battery-supported grid-tied rooftop Photovoltaic (PV) system, sold by a commercial vendor. SRP believes this system has the potential to satisfy the needs of its customers, who opt for utilizing solar power to partially satisfy their power needs.

An important part of this elaborate project is the development of a new load forecasting algorithm and a better control strategy for the optimized utilization of the storage system. The built-in algorithm of this commercial unit uses simple forecasting and battery control strategies. With the recent improvement in Machine Learning (ML) techniques, development of a more sophisticated model of the problem in hand was possible. This research is aimed at achieving the goal by utilizing the appropriate ML techniques to better model the problem, which will essentially result in a better solution. In this research, a set of six unique features are used to model the load forecasting problem and different ML algorithms are simulated on the developed model. A similar approach is taken to solve the PV prediction problem. Finally, a very effective battery control strategy is built (utilizing the results of the load and PV forecasting), with the aim of ensuring a reduction in the amount of energy consumed from the grid during the “on-peak” hours. Apart from the reduction in the energy consumption, this battery control algorithm decelerates the “cycling aging” or the aging of the battery owing to the charge/dis-charges cycles endured by selectively charging/dis-charging the battery based on need.

ii

The results of this proposed strategy are verified using a hardware implementation (the PV system was coupled with a custom-built load bank and this setup was used to simulate a house). The results pertaining to the performances of the built-in algorithm and the ML algorithm are compared and the economic analysis is performed. The findings of this research have in the process of being published in a reputed journal.
ContributorsHariharan, Aashiek (Author) / Karady, George G. (Thesis advisor) / Heydt, Gerald Thomas (Committee member) / Qin, Jiangchao (Committee member) / Allee, David R. (Committee member) / Arizona State University (Publisher)
Created2018
154055-Thumbnail Image.png
Description
The electromagnetic fields near power lines that may produce adverse effects on humans are of increasing interest in a variety of situations, thus making it worthwhile to develop general-purpose software that estimates both the electric and magnetic fields accurately. This study deals with the simulations of the electric and magnetic

The electromagnetic fields near power lines that may produce adverse effects on humans are of increasing interest in a variety of situations, thus making it worthwhile to develop general-purpose software that estimates both the electric and magnetic fields accurately. This study deals with the simulations of the electric and magnetic fields near high-voltage power lines for the triangular, horizontal and vertical conductor arrangements under both balanced and unbalanced conditions.

For all three conductor arrangements, the shapes of the electric field distribution curves are different with the vertical arrangement best for minimizing right of way consideration, while the shapes of the magnetic field distributions curves are similar. Except for the horizontal arrangement, the maximum electric field magnitudes with shield conductors are larger than those without shield conductors. Among the three different arrangements, the maximum field value of the vertical arrangement is most vulnerable to the unbalanced conditions.

For both the electric and magnetic fields, increasing the heights of phase conductors gradually results in diminishing return in terms of the field reduction. In this work, both the maximum electric field magnitudes and the maximum magnetic field magnitudes produced by 500 kV power lines at 1 m height from the ground are all within the permissible exposure levels for the general public. At last, the dynamic trajectories of both fields with time are simulated and interpreted, with each field represented by a vector rotating in a plane describing an ellipse, where the vector values can be compared to high-speed vector measurements.
ContributorsXiao, Lei (Author) / Holbert, Keith E. (Thesis advisor) / Karady, George G. (Committee member) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2015
154077-Thumbnail Image.png
Description
ABSTRACT

This dissertation introduces a real-time topology monitoring scheme for power systems intended to provide enhanced situational awareness during major system disturbances. The topology monitoring scheme requires accurate real-time topology information to be effective. This scheme is supported by advances in transmission line outage detection based on data-mining phasor measurement unit

ABSTRACT

This dissertation introduces a real-time topology monitoring scheme for power systems intended to provide enhanced situational awareness during major system disturbances. The topology monitoring scheme requires accurate real-time topology information to be effective. This scheme is supported by advances in transmission line outage detection based on data-mining phasor measurement unit (PMU) measurements.

A network flow analysis scheme is proposed to track changes in user defined minimal cut sets within the system. This work introduces a new algorithm used to update a previous network flow solution after the loss of a single system branch. The proposed new algorithm provides a significantly decreased solution time that is desired in a real- time environment. This method of topology monitoring can provide system operators with visual indications of potential problems in the system caused by changes in topology.

This work also presents a method of determining all singleton cut sets within a given network topology called the one line remaining (OLR) algorithm. During operation, if a singleton cut set exists, then the system cannot withstand the loss of any one line and still remain connected. The OLR algorithm activates after the loss of a transmission line and determines if any singleton cut sets were created. These cut sets are found using properties of power transfer distribution factors and minimal cut sets.

The topology analysis algorithms proposed in this work are supported by line outage detection using PMU measurements aimed at providing accurate real-time topology information. This process uses a decision tree (DT) based data-mining approach to characterize a lost tie line in simulation. The trained DT is then used to analyze PMU measurements to detect line outages. The trained decision tree was applied to real PMU measurements to detect the loss of a 500 kV line and had no misclassifications.

The work presented has the objective of enhancing situational awareness during significant system disturbances in real time. This dissertation presents all parts of the proposed topology monitoring scheme and justifies and validates the methodology using a real system event.
ContributorsWerho, Trevor Nelson (Author) / Vittal, Vijay (Thesis advisor) / Heydt, Gerald (Committee member) / Hedman, Kory (Committee member) / Karady, George G. (Committee member) / Arizona State University (Publisher)
Created2015
153938-Thumbnail Image.png
Description
Shunt capacitors are often added in transmission networks at suitable locations to improve the voltage profile. In this thesis, the transmission system in Arizona is considered as a test bed. Many shunt capacitors already exist in the Arizona transmission system and more are planned to be added. Addition of

Shunt capacitors are often added in transmission networks at suitable locations to improve the voltage profile. In this thesis, the transmission system in Arizona is considered as a test bed. Many shunt capacitors already exist in the Arizona transmission system and more are planned to be added. Addition of these shunt capacitors may create resonance conditions in response to harmonic voltages and currents. Such resonance, if it occurs, may create problematic issues in the system. It is main objective of this thesis to identify potential problematic effects that could occur after placing new shunt capacitors at selected buses in the Arizona network. Part of the objective is to create a systematic plan for avoidance of resonance issues.

For this study, a method of capacitance scan is proposed. The bus admittance matrix is used as a model of the networked transmission system. The calculations on the admittance matrix were done using Matlab. The test bed is the actual transmission system in Arizona; however, for proprietary reasons, bus names are masked in the thesis copy in-tended for the public domain. The admittance matrix was obtained from data using the PowerWorld Simulator after equivalencing the 2016 summer peak load (planning case). The full Western Electricity Coordinating Council (WECC) system data were used. The equivalencing procedure retains only the Arizona portion of the WECC.

The capacitor scan results for single capacitor placement and multiple capacitor placement cases are presented. Problematic cases are identified in the form of ‘forbidden response. The harmonic voltage impact of known sources of harmonics, mainly large scale HVDC sources, is also presented.

Specific key results for the study indicated include:

• The forbidden zones obtained as per the IEEE 519 standard indicates the bus 10 to be the most problematic bus.

• The forbidden zones also indicate that switching values for the switched shunt capacitor (if used) at bus 3 should be should be considered carefully to avoid resonance condition from existing.

• The highest sensitivity of 0.0033 per unit for HVDC sources of harmonics was observed at bus 7 when all the HVDC sources were active at the same time.
ContributorsPatil, Hardik U (Author) / Heydt, Gerald T (Thesis advisor) / Karady, George G. (Committee member) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2015
153878-Thumbnail Image.png
Description
The utilization of power cables is increasing with the development of renewable energy and the maintenance replacement of old overhead power lines. Therefore, effective monitoring and accurate fault location for power cables are very important for the sake of a stable power supply.

The recent technologies for power cable diagnosis

The utilization of power cables is increasing with the development of renewable energy and the maintenance replacement of old overhead power lines. Therefore, effective monitoring and accurate fault location for power cables are very important for the sake of a stable power supply.

The recent technologies for power cable diagnosis and temperature monitoring system are described including their intrinsic limitations for cable health assessment. Power cable fault location methods are reviewed with two main categories: off-line and on-line data based methods.

As a diagnostic and fault location approach, a new passive methodology is introduced. This methodology is based on analyzing the resonant frequencies of the transfer function between the input and output of the power cable system. The equivalent pi model is applied to the resonant frequency calculation for the selected underground power cable transmission system.

The characteristics of the resonant frequencies are studied by analytical derivations and PSCAD simulations. It is found that the variation of load magnitudes and change of positive power factors (i.e., inductive loads) do not affect resonant frequencies significantly, but there is considerable movement of resonant frequencies under change of negative power factors (i.e., capacitive loads).

Power cable fault conditions introduce new resonant frequencies in accordance with fault positions. Similar behaviors of the resonant frequencies are shown in a transformer (TR) connected power cable system with frequency shifts caused by the TR impedance.

The resonant frequencies can be extracted by frequency analysis of power signals and the inherent noise in these signals plays a key role to measure the resonant frequencies. Window functions provide an effective tool for improving resonant frequency discernment. The frequency analysis is implemented on noise laden PSCAD simulation signals and it reveals identical resonant frequency characteristics with theoretical studies.

Finally, the noise levels of real voltage and current signals, which are acquired from an operating power plant, are estimated and the resonant frequencies are extracted by applying window functions, and these results prove that the resonant frequency can be used as an assessment for the internal changes in power cable parameters such as defects and faults.
ContributorsKim, Youngdeug (Author) / Holbert, Keith Edwin (Thesis advisor) / Papandreou-Suppappola, Antonia (Committee member) / Heydt, Gerald (Committee member) / Karady, George G. (Committee member) / Arizona State University (Publisher)
Created2015
153925-Thumbnail Image.png
Description
This thesis provides a cost to benefit analysis of the proposed next generation of distribution systems- the Future Renewable Electric Energy Distribution Management (FREEDM) system. With the increasing penetration of renewable energy sources onto the grid, it becomes necessary to have an infrastructure that allows for easy integration of these

This thesis provides a cost to benefit analysis of the proposed next generation of distribution systems- the Future Renewable Electric Energy Distribution Management (FREEDM) system. With the increasing penetration of renewable energy sources onto the grid, it becomes necessary to have an infrastructure that allows for easy integration of these resources coupled with features like enhanced reliability of the system and fast pro-tection from faults. The Solid State Transformer (SST) and the Fault Isolation Device (FID) make for the core of the FREEDM system and have huge investment costs.

Some key features of the FREEDM system include improved power flow control, compact design and unity power factor operation. Customers may observe a reduction in the electricity bill by a certain fraction for using renewable sources of generation. There is also a possibility of huge subsidies given to encourage use of renewable energy. This thesis is an attempt to quantify the benefits offered by the FREEDM system in monetary terms and to calculate the time in years required to gain a return on investments made. The elevated cost of FIDs needs to be justified by the advantages they offer. The result of different rates of interest and how they influence the payback period is also studied. The payback periods calculated are observed for viability. A comparison is made between the active power losses on a certain distribution feeder that makes use of distribution level magnetic transformers versus one that makes use of SSTs. The reduction in the annual active power losses in the case of the feeder using SSTs is translated onto annual savings in terms of cost when compared to the conventional case with magnetic transformers. Since the FREEDM system encourages operation at unity power factor, the need for installing capacitor banks for improving the power factor is eliminated and this re-flects in savings in terms of cost. The FREEDM system offers enhanced reliability when compared to a conventional system. The payback periods observed support the concept of introducing the FREEDM system.
ContributorsRaman, Apurva (Author) / Heydt, Gerald (Thesis advisor) / Karady, George G. (Committee member) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2015
154180-Thumbnail Image.png
Description
Underground transmission cables in power systems are less likely to experience electrical faults, however, resulting outage times are much greater in the event that a failure does occur. Unlike overhead lines, underground cables are not self-healing from flashover events. The faulted section must be located and repaired before the line

Underground transmission cables in power systems are less likely to experience electrical faults, however, resulting outage times are much greater in the event that a failure does occur. Unlike overhead lines, underground cables are not self-healing from flashover events. The faulted section must be located and repaired before the line can be put back into service. Since this will often require excavation of the underground duct bank, the procedure to repair the faulted section is both costly and time consuming. These added complications are the prime motivators for developing accurate and reliable ratings for underground cable circuits.

This work will review the methods by which power ratings, or ampacity, for underground cables are determined and then evaluate those ratings by making comparison with measured data taken from an underground 69 kV cable, which is part of the Salt River Project (SRP) power subtransmission system. The process of acquiring, installing, and commissioning the temperature monitoring system is covered in detail as well. The collected data are also used to evaluate typical assumptions made when determining underground cable ratings such as cable hot-spot location and ambient temperatures.

Analysis results show that the commonly made assumption that the deepest portion of an underground power cable installation will be the hot-spot location does not always hold true. It is shown that distributed cable temperature measurements can be used to locate the proper line segment to be used for cable ampacity calculations.
ContributorsStowers, Travis (Author) / Tylavsky, Daniel (Thesis advisor) / Karady, George G. (Committee member) / Holbert, Keith E. (Committee member) / Arizona State University (Publisher)
Created2015
154270-Thumbnail Image.png
Description
Electric substation physical plans are developed with consideration given to lightning protection. To develop these plans utility design engineers use various methods. This thesis focuses on developing a computer program for two methods/models for substation shielding against direct lightning strokes. The first method is being used currently in the industry

Electric substation physical plans are developed with consideration given to lightning protection. To develop these plans utility design engineers use various methods. This thesis focuses on developing a computer program for two methods/models for substation shielding against direct lightning strokes. The first method is being used currently in the industry to protect the substation structures. The second model is a new and more physics based approach towards lightning phenomenon. Both the methods consider only direct lightning strikes that can hit the substation equipment. Hence, the travelling waves, indirect strokes or over-voltage arriving at the substation equipment are not considered. The Electro-Geometric method (EGM) based Rolling Sphere Method (RSM) is used to develop first part of the program. The aim of the program is to design the protection system for the substation equipment quickly and error free. The protection system uses lightning masts and/or shield wires to protect the station equipment. These are grounded solidly with low impedance to earth. The MATLAB based program gives a two dimensional visual representation of the zone of protection and therefore helps utility engineers to position shielding system. As this program is converted further into an executable file, it can be used on any computer to produce the results without need of any other software. The second part of the thesis focuses on developing the MATLAB code for protection of substation equipment using the Rizk model which is not used as of now for shielding system design in industry. Using more physics based model, simulation of downward lightning leader and connecting upward leader is shown.

Finally both the methods are compared. This includes consideration of a 220 kV substation layout arrangement. The equipment are protected using shielding masts and the comparison is made in terms of number of the protective equipment needed. It is found that the classical rolling sphere model gives more conservative results than the physics based model. Hence the results shows that it is possible to use present methods and still protect the equipment sufficiently.
ContributorsMarathe, Vinit (Author) / Karady, George G. (Thesis advisor) / Ayyanar, Raja (Committee member) / Holbert, Keith E. (Committee member) / Arizona State University (Publisher)
Created2016