Matching Items (11)
Filtering by

Clear all filters

150094-Thumbnail Image.png
Description
The high penetration of photovoltaic (PV) both at the utility and at the distribu-tion levels, has raised concerns about the reliability of grid-tied inverters of PV power systems. Inverters are generally considered as the weak link in PV power systems. The lack of a dedicated qualification/reliability standard for PV inverters

The high penetration of photovoltaic (PV) both at the utility and at the distribu-tion levels, has raised concerns about the reliability of grid-tied inverters of PV power systems. Inverters are generally considered as the weak link in PV power systems. The lack of a dedicated qualification/reliability standard for PV inverters is a main barrier in realizing higher level of confidence in reliability. Development of a well-accepted design qualification standard specifically for PV inverters will help pave the way for significant improvement in reliability and performance of inverters across the entire industry. The existing standards for PV inverters such as UL 1741 and IEC 62109-1 primarily focus on safety. IEC 62093 discusses inverter qualification but it includes all the balance of sys-tem components and therefore not specific to PV inverters. There are other general stan-dards for distributed generators including the IEEE1547 series of standards which cover major concerns like utility integration but they are not dedicated to PV inverters and are not written from a design qualification point of view. In this thesis, some of the potential requirements for a design qualification standard for PV inverters are addressed. The IEC 62093 is considered as a guideline and the possible inclusions in the framework for a dedicated design qualification standard of PV inverter are discussed. The missing links in existing PV inverter related standards are identified by performing gap analysis. Dif-ferent requirements of small residential inverters compared to large utility-scale systems, and the emerging requirements on grid support features are also considered. Electric stress test is found to be the key missing link and one of the electric stress tests, the surge withstand test is studied in detail. The use of the existing standards for surge withstand test of residential scale PV inverters is investigated and a method to suitably adopt these standards is proposed. The proposed method is studied analytically and verified using simulation. A design criterion for choosing the switch ratings of the inverter that can per-form reliably under the surge environment is derived.
ContributorsAlampoondi Venkataramanan, Sai Balasubramanian (Author) / Ayyanar, Raja (Thesis advisor) / Vittal, Vijay (Committee member) / Heydt, Gerald (Committee member) / Arizona State University (Publisher)
Created2011
152318-Thumbnail Image.png
Description
This study evaluates two photovoltaic (PV) power plants based on electrical performance measurements, diode checks, visual inspections and infrared scanning. The purpose of this study is to measure degradation rates of performance parameters (Pmax, Isc, Voc, Vmax, Imax and FF) and to identify the failure modes in a "hot-dry desert"

This study evaluates two photovoltaic (PV) power plants based on electrical performance measurements, diode checks, visual inspections and infrared scanning. The purpose of this study is to measure degradation rates of performance parameters (Pmax, Isc, Voc, Vmax, Imax and FF) and to identify the failure modes in a "hot-dry desert" climatic condition along with quantitative determination of safety failure rates and reliability failure rates. The data obtained from this study can be used by module manufacturers in determining the warranty limits of their modules and also by banks, investors, project developers and users in determining appropriate financing or decommissioning models. In addition, the data obtained in this study will be helpful in selecting appropriate accelerated stress tests which would replicate the field failures for the new modules and would predict the lifetime for new PV modules. The study was conducted at two, single axis tracking monocrystalline silicon (c-Si) power plants, Site 3 and Site 4c of Salt River Project (SRP). The Site 3 power plant is located in Glendale, Arizona and the Site 4c power plant is located in Mesa, Arizona both considered a "hot-dry" field condition. The Site 3 power plant has 2,352 modules (named as Model-G) which was rated at 250 kW DC output. The mean and median degradation of these 12 years old modules are 0.95%/year and 0.96%/year, respectively. The major cause of degradation found in Site 3 is due to high series resistance (potentially due to solder-bond thermo-mechanical fatigue) and the failure mode is ribbon-ribbon solder bond failure/breakage. The Site 4c power plant has 1,280 modules (named as Model-H) which provide 243 kW DC output. The mean and median degradation of these 4 years old modules are 0.96%/year and 1%/year, respectively. At Site 4c, practically, none of the module failures are observed. The average soiling loss is 6.9% in Site 3 and 5.5% in Site 4c. The difference in soiling level is attributed to the rural and urban surroundings of these two power plants.
ContributorsMallineni, Jaya Krishna (Author) / Govindasamy, Tamizhmani (Thesis advisor) / Devarajan, Srinivasan (Committee member) / Narciso, Macia (Committee member) / Arizona State University (Publisher)
Created2013
152326-Thumbnail Image.png
Description
Solar power generation is the most promising technology to transfer energy consumption reliance from fossil fuel to renewable sources. Concentrated solar power generation is a method to concentrate the sunlight from a bigger area to a smaller area. The collected sunlight is converted more efficiently through two types of technologies:

Solar power generation is the most promising technology to transfer energy consumption reliance from fossil fuel to renewable sources. Concentrated solar power generation is a method to concentrate the sunlight from a bigger area to a smaller area. The collected sunlight is converted more efficiently through two types of technologies: concentrated solar photovoltaics (CSPV) and concentrated solar thermal power (CSTP) generation. In this thesis, these two technologies were evaluated in terms of system construction, performance characteristics, design considerations, cost benefit analysis and their field experience. The two concentrated solar power generation systems were implemented with similar solar concentrators and solar tracking systems but with different energy collecting and conversion components: the CSPV system uses high efficiency multi-junction solar cell modules, while the CSTP system uses a boiler -turbine-generator setup. The performances are calibrated via the experiments and evaluation analysis.
ContributorsJin, Zhilei (Author) / Hui, Yu (Thesis advisor) / Ayyanar, Raja (Committee member) / Rodriguez, Armando (Committee member) / Arizona State University (Publisher)
Created2013
152329-Thumbnail Image.png
Description
This study evaluates two 16 year old photovoltaic power (PV) plants to ascertain degradation rates and various failure modes which occur in a "hot-dry" climate. The data obtained from this study can be used by module manufacturers in determining the warranty limits of their modules and also by banks, investors,

This study evaluates two 16 year old photovoltaic power (PV) plants to ascertain degradation rates and various failure modes which occur in a "hot-dry" climate. The data obtained from this study can be used by module manufacturers in determining the warranty limits of their modules and also by banks, investors, project developers and users in determining appropriate financing or decommissioning models. In addition, the data obtained in this study will be helpful in selecting appropriate accelerated stress tests which would replicate the field failures for the new modules and would predict the lifetime for new PV modules. The two power plants referred to as Site 4A and -4B with (1512 modules each) were initially installed on a single axis tracking system in Gilbert, Arizona for the first seven years and have been operating at their current location in Mesa, Arizona for the last nine years at fixed horizontal tilt Both sites experience hot-dry desert climate. Average degradation rate is 0.85%/year for the best modules and 1.1%/year for all the modules (excluding the safety failed modules). Primary safety failure mode is the backsheet delamination though it is small (less than 1.7%). Primary degradation mode and reliability failure mode may potentially be attributed to encapsulant browning leading to transmittance/current loss and thermo-mechanical solder bond fatigue (cell-ribbon and ribbon-ribbon) leading to series resistance increase. Average soiling loss of horizontal tilt based modules is 11.1%. About 0.5-1.7% of the modules qualify for the safety returns under the typical 20/20 warranty terms, 73-76% of the modules qualify for the warranty claims under the typical 20/20 power warranty terms and 24-26% of the modules are meeting the typical 20/20 power warranty terms.
ContributorsYedidi, Karan Rao (Author) / Govindasamy, Tamizhmani (Thesis advisor) / Devarajan, Srinivasan (Committee member) / Narciso, Macia (Committee member) / Arizona State University (Publisher)
Created2013
152012-Thumbnail Image.png
Description
As renewable energy becomes more prevalent in transmission and distribution systems, it is vital to understand the uncertainty and variability that accompany these resources. Microgrids have the potential to mitigate the effects of resource uncertainty. With the ability to exist in either an islanded mode or maintain connections with the

As renewable energy becomes more prevalent in transmission and distribution systems, it is vital to understand the uncertainty and variability that accompany these resources. Microgrids have the potential to mitigate the effects of resource uncertainty. With the ability to exist in either an islanded mode or maintain connections with the main-grid, a microgrid can increase reliability, defer T&D; infrastructure and effectively utilize demand response. This study presents a co-optimization framework for a microgrid with solar photovoltaic generation, emergency generation, and transmission switching. Today unit commitment models ensure reliability with deterministic criteria, which are either insufficient to ensure reliability or can degrade economic efficiency for a microgrid that uses a large penetration of variable renewable resources. A stochastic mixed integer linear program for day-ahead unit commitment is proposed to account for uncertainty inherent in PV generation. The model incorporates the ability to trade energy and ancillary services with the main-grid, including the designation of firm and non-firm imports, which captures the ability to allow for reserve sharing between the two systems. In order to manage the computational complexities, a Benders' decomposition approach is utilized. The commitment schedule was validated with solar scenario analysis, i.e., Monte-Carlo simulations are conducted to test the proposed dispatch solution. For this test case, there were few deviations to power imports, 0.007% of solar was curtailed, no load shedding occurred in the main-grid, and 1.70% load shedding occurred in the microgrid.
ContributorsHytowitz, Robin Broder (Author) / Hedman, Kory W (Thesis advisor) / Heydt, Gerald T (Committee member) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2013
150530-Thumbnail Image.png
Description
With increased usage of green energy, the number of photovoltaic arrays used in power generation is increasing rapidly. Many of the arrays are located at remote locations where faults that occur within the array often go unnoticed and unattended for large periods of time. Technicians sent to rectify the faults

With increased usage of green energy, the number of photovoltaic arrays used in power generation is increasing rapidly. Many of the arrays are located at remote locations where faults that occur within the array often go unnoticed and unattended for large periods of time. Technicians sent to rectify the faults have to spend a large amount of time determining the location of the fault manually. Automated monitoring systems are needed to obtain the information about the performance of the array and detect faults. Such systems must monitor the DC side of the array in addition to the AC side to identify non catastrophic faults. This thesis focuses on two of the requirements for DC side monitoring of an automated PV array monitoring system. The first part of the thesis quantifies the advantages of obtaining higher resolution data from a PV array on detection of faults. Data for the monitoring system can be gathered for the array as a whole or from additional places within the array such as individual modules and end of strings. The fault detection rate and the false positive rates are compared for array level, string level and module level PV data. Monte Carlo simulations are performed using PV array models developed in Simulink and MATLAB for fault and no fault cases. The second part describes a graphical user interface (GUI) that can be used to visualize the PV array for module level monitoring system information. A demonstration GUI is built in MATLAB using data obtained from a PV array test facility in Tempe, AZ. Visualizations are implemented to display information about the array as a whole or individual modules and locate faults in the array.
ContributorsKrishnan, Venkatachalam (Author) / Tepedelenlioğlu, Cihan (Thesis advisor) / Spanias, Andreas (Thesis advisor) / Ayyanar, Raja (Committee member) / Papandreou-Suppappola, Antonia (Committee member) / Arizona State University (Publisher)
Created2012
149394-Thumbnail Image.png
Description
Market acceptability of distributed energy resource (DER) technologies and the gradual and consistent increase in their depth of penetration have generated significant interest over the past few years. In particular, in Arizona and several other states there has been a substantial in-crease in distributed photovoltaic (PV) generation interfaced to the

Market acceptability of distributed energy resource (DER) technologies and the gradual and consistent increase in their depth of penetration have generated significant interest over the past few years. In particular, in Arizona and several other states there has been a substantial in-crease in distributed photovoltaic (PV) generation interfaced to the power distribution systems, and is expected to continue to grow at a significant rate. This has made integration, control and optimal operation of DER units a main area of focus in the design and operation of distribution systems. Grid-connected, distributed PV covers a wide range of power levels ranging from small, single phase residential roof-top systems to large three-phase, multi-megawatt systems. The focus of this work is on analyzing large, three-phase systems, with the power distribution system of the Arizona State University (ASU) Tempe campus used as the test bed for analysis and simulation. The Tempe campus of ASU has presently 4.5 MW of installed PV capacity, with another 4.5 MW expected to be added by 2011, which will represent about 22% of PV penetration. The PV systems are interfaced to the grid invariably by a power electronic inverter. Many of the important characteristics of the PV generation are influenced by the design and performance of the inverter, and hence suitable models of the inverter are needed to analyze PV systems. Several models of distributed generation (DG), including switching and average models, suitable for different study objectives, and different control modes of the inverter have been described in this thesis. A critical function of the inverters is to quickly detect and eliminate unintentional islands during grid failure. In this thesis, many active anti-islanding techniques with voltage and frequency positive feedback have been studied. Effectiveness of these techniques in terms of the tripping times specified in IEEE Std. 1547 for interconnecting distributed resources with electric power systems has been analyzed. The impact of distributed PV on the voltage profile of a distribution system has been ana-lyzed with ASU system as the test bed using power systems analysis tools namely PowerWorld and CYMDIST. The present inverters complying with IEEE 1547 do not regulate the system vol-tage. However, the future inverters especially at higher power levels are expected to perform sev-eral grid support functions including voltage regulation and reactive power support. Hence, the impact of inverters with the reactive power support capabilities is also analyzed. Various test sce-narios corresponding to different grid conditions are simulated and it is shown that distributed PV improves the voltage profile of the system. The improvements are more significant when the PV generators are capable of reactive power support. Detailed short circuit analyses are also per-formed on the system, and the impact of distributed PV on the fault current magnitude, with and without reactive power injection, have been studied.
ContributorsNarayanan, Anand (Author) / Ayyanar, Raja (Thesis advisor) / Vittal, Vijay (Committee member) / Heydt, Gerald T (Committee member) / Arizona State University (Publisher)
Created2010
154123-Thumbnail Image.png
Description
This is a two part thesis:

Part – I

This part of the thesis involves automation of statistical risk analysis of photovoltaic (PV) power plants. Statistical risk analysis on the field observed defects/failures in the PV power plants is usually carried out using a combination of several manual methods which are often

This is a two part thesis:

Part – I

This part of the thesis involves automation of statistical risk analysis of photovoltaic (PV) power plants. Statistical risk analysis on the field observed defects/failures in the PV power plants is usually carried out using a combination of several manual methods which are often laborious, time consuming and prone to human errors. In order to mitigate these issues, an automated statistical risk analysis (FMECA) is necessary. The automation developed and presented in this project generates about 20 different reliability risk plots in about 3-4 minutes without the need of several manual labor hours traditionally spent for these analyses. The primary focus of this project is to automatically generate Risk Priority Number (RPN) for each defect/failure based on two Excel spreadsheets: Defect spreadsheet; Degradation rate spreadsheet. Automation involves two major programs – one to calculate Global RPN (Sum of Performance RPN and Safety RPN) and the other to find the correlation of defects with I-V parameters’ degradations. Based on the generated RPN and other reliability plots, warranty claims for material defect and degradation rate may be made by the system owners.

Part – II

This part of the thesis involves the evaluation of Module Level Power Electronics (MLPE) which are commercially available and used by the industry. Reliability evaluations of any product typically involve pre-characterizations, many different accelerated stress tests and post-characterizations. Due to time constraints, this part of the project was limited to only pre-characterizations of about 100 MLPE units commercially available from 5 different manufacturers. Pre-characterizations involve testing MLPE units for rated efficiency, CEC efficiency, power factor and Harmonics (Vthd (%) and Ithd (%)). The pre-characterization test results can be used to validate manufacturer claims and to evaluate the product for compliance certification test standards. Pre-characterization results were compared for all MLPE units individually for all tested parameters listed above. The accelerated stress tests are ongoing and are not presented in this thesis. Based on the pre-characterizations presented in this report and post-characterizations performed after the stress tests, the pass/fail and time-to-failure analyses can be carried out by future researchers.
ContributorsMoorthy, Mathan Kumar (Author) / Govindasamy, Tamizhmani (Thesis advisor) / Devarajan, Srinivasan (Committee member) / Bradley, Rogers (Committee member) / Arizona State University (Publisher)
Created2015
154933-Thumbnail Image.png
Description
Due to the increasing trend of electricity price for the future and the price reduction of solar electronics price led by the policy stimulus and the technological improvement, the residential distribution solar photovoltaic (PV) system’s market is prosperous. Excess energy can be sold back to the grid, however peak demand

Due to the increasing trend of electricity price for the future and the price reduction of solar electronics price led by the policy stimulus and the technological improvement, the residential distribution solar photovoltaic (PV) system’s market is prosperous. Excess energy can be sold back to the grid, however peak demand of a residential customer typically occurs in late afternoon/early evening when PV systems are not a productive. The solar PV system can provide residential customers sufficient energy during the daytime, even the exceeding energy can be sold back to the grid especially during the day with good sunlight, however, the peak demand of a regular family always appears during late afternoon and early evening which are not productive time for PV system. In this case, the PV customers only need the grid energy when other customers also need it the most. Because of the lower contribution of PV systems during times of peak demand, utilities are beginning to adjust rate structures to better align the bills paid by PV customers with the cost to the utility to serve those customers. Different rate structures include higher fixed charges, higher on-peak electricity prices, on-peak demand charges, or prices based on avoided costs. The demand charge and the on-peak energy charge significantly reduced the savings brought by the PV system. This will result in a longer the customer’s payback period. Eventually PV customers are not saving a lot in their electricity bill compare to those customers who do not own a PV system.



A battery system is a promising technology that can improve monthly bill savings since a battery can store the solar energy and the off-peak grid energy and release it later during the on-peak hours. Sponsored by Salt River Project (SRP), a smart home model consists 1.35 kW PV panels, a 7.76 kWh lithium-ion battery and an adjustable resistive load bank was built on the roof of Engineering Research Center (ERC) building. For analysis, data was scaled up by 6/1.35 times to simulate a real residential PV setup. The testing data had been continuously recorded for more than one year (Aug.2014 - Oct.2015) and a battery charging strategy was developed based on those data. The work of this thesis deals with the idea of this charging strategy and the economic benefits this charging strategy can bring to the PV customers. Part of this research work has been wrote into a conference paper which is accepted by IEEE PES General Meeting 2016. A new and larger system has been installed on the roof with 6 kW PV modules and 6 kW output integrated electronics. This project will go on and the method come up by this thesis will be tested.
ContributorsWang, Xin'an (Author) / Karady, George G. (Thesis advisor) / Smedley, Grant (Committee member) / Qin, Jiangchao (Committee member) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2016
152908-Thumbnail Image.png
Description
A new photovoltaic (PV) array power converter circuit is presented. The salient features of this inverter are: transformerless topology, grounded PV array, and only film capacitors. The motivations are to reduce cost, eliminate leakage ground currents, and improve reliability. The use of Silicon Carbide (SiC) transistors is the key enabling

A new photovoltaic (PV) array power converter circuit is presented. The salient features of this inverter are: transformerless topology, grounded PV array, and only film capacitors. The motivations are to reduce cost, eliminate leakage ground currents, and improve reliability. The use of Silicon Carbide (SiC) transistors is the key enabling technology for this particular circuit to attain good efficiency.

Traditionally, grid connected PV inverters required a transformer for isolation and safety. The disadvantage of high frequency transformer based inverters is complexity and cost. Transformerless inverters have become more popular recently, although they can be challenging to implement because of possible high frequency currents through the PV array's stay capacitance to earth ground. Conventional PV inverters also typically utilize electrolytic capacitors for bulk power buffering. However such capacitors can be prone to decreased reliability.

The solution proposed here to solve these problems is a bi directional buck boost converter combined with half bridge inverters. This configuration enables grounding of the array's negative terminal and passive power decoupling with only film capacitors.

Several aspects of the proposed converter are discussed. First a literature review is presented on the issues to be addressed. The proposed circuit is then presented and examined in detail. This includes theory of operation, component selection, and control systems. An efficiency analysis is also conducted. Simulation results are then presented that show correct functionality. A hardware prototype is built and experiment results also prove the concept. Finally some further developments are mentioned.

As a summary of the research a new topology and control technique were developed. The resultant circuit is a high performance transformerless PV inverter with upwards of 97% efficiency.
ContributorsBreazeale, Lloyd C (Author) / Ayyanar, Raja (Thesis advisor) / Karady, George G. (Committee member) / Tylavsky, Daniel (Committee member) / Tsakalis, Konstantinos (Committee member) / Arizona State University (Publisher)
Created2014