Filtering by
- All Subjects: Electric power transmission
- Creators: Hedman, Kory W
- Creators: Kosut, Oliver
- Member of: Theses and Dissertations
- Member of: Barrett, The Honors College Thesis/Creative Project Collection
- Resource Type: Text
Two general approaches are developed. Both approximate the effects of recourse decisions without actually solving a stochastic model. The first approach procures more reserve whenever approximate recourse policies stress the transmission network. The second approach procures reserve at prime locations by generalizing the existing practice of reserve disqualification. The latter approach is applied for feasibility and is later extended to limit scenario costs. Testing demonstrates expected cost improvements around 0.5%-1.0% for the IEEE 73-bus test case, which can translate to millions of dollars per year even for modest systems. The heuristics developed in this dissertation perform somewhere between established deterministic and stochastic models: providing an economic benefit over current practices without substantially increasing computational times.
transportation of power from the sources of power generation via an intermediate
densely connected transmission network to a large distribution network of end-users
at the lowest level of the hierarchy. At each level of the hierarchy (generation/ trans-
mission/ distribution), the system is managed and monitored with a combination of
(a) supervisory control and data acquisition (SCADA); and (b) energy management
systems (EMSs) that process the collected data and make control and actuation de-
cisions using the collected data. However, at all levels of the hierarchy, both SCADA
and EMSs are vulnerable to cyber attacks. Furthermore, given the criticality of the
electric power infrastructure, cyber attacks can have severe economic and social con-
sequences.
This thesis focuses on cyber attacks on SCADA and EMS at the transmission
level of the electric power system. The goal is to study the consequences of three
classes of cyber attacks that can change topology data. These classes include: (i)
unobservable state-preserving cyber attacks that only change the topology data; (ii)
unobservable state-and-topology cyber-physical attacks that change both states and
topology data to enable a coordinated physical and cyber attack; and (iii) topology-
targeted man-in-the-middle (MitM) communication attacks that alter topology data
shared during inter-EMS communication. Specically, attack class (i) and (ii) focus on
the unobservable attacks on single regional EMS while class (iii) focuses on the MitM
attacks on communication links between regional EMSs. For each class of attacks,
the theoretical attack model and the implementation of attacks are provided, and the
worst-case attack and its consequences are exhaustively studied. In particularly, for
class (ii), a two-stage optimization problem is introduced to study worst-case attacks
that can cause a physical line over
ow that is unobservable in the cyber layer. The long-term implication and the system anomalies are demonstrated via simulation.
For attack classes (i) and (ii), both mathematical and experimental analyses sug-
gest that these unobservable attacks can be limited or even detected with resiliency
mechanisms including load monitoring, anomalous re-dispatches checking, and his-
torical data comparison. For attack class (iii), countermeasures including anomalous
tie-line interchange verication, anomalous re-dispatch alarms, and external contin-
gency lists sharing are needed to thwart such attacks.
power, gas , communication networks. Ensuring the security of these
infrastructures is of utmost importance. This task becomes ever more challenging as
the inter-dependence among these infrastructures grows and a security breach in one
infrastructure can spill over to the others. The implication is that the security practices/
analysis recommended for these infrastructures should be done in coordination.
This thesis, focusing on the power grid, explores strategies to secure the system that
look into the coupling of the power grid to the cyber infrastructure, used to manage
and control it, and to the gas grid, that supplies an increasing amount of reserves to
overcome contingencies.
The first part (Part I) of the thesis, including chapters 2 through 4, focuses on
the coupling of the power and the cyber infrastructure that is used for its control and
operations. The goal is to detect malicious attacks gaining information about the
operation of the power grid to later attack the system. In chapter 2, we propose a
hierarchical architecture that correlates the analysis of high resolution Micro-Phasor
Measurement Unit (microPMU) data and traffic analysis on the Supervisory Control
and Data Acquisition (SCADA) packets, to infer the security status of the grid and
detect the presence of possible intruders. An essential part of this architecture is
tied to the analysis on the microPMU data. In chapter 3 we establish a set of anomaly
detection rules on microPMU data that
flag "abnormal behavior". A placement strategy
of microPMU sensors is also proposed to maximize the sensitivity in detecting anomalies.
In chapter 4, we focus on developing rules that can localize the source of an events
using microPMU to further check whether a cyber attack is causing the anomaly, by
correlating SCADA traffic with the microPMU data analysis results. The thread that
unies the data analysis in this chapter is the fact that decision are made without fully estimating the state of the system; on the contrary, decisions are made using
a set of physical measurements that falls short by orders of magnitude to meet the
needs for observability. More specifically, in the first part of this chapter (sections 4.1-
4.2), using microPMU data in the substation, methodologies for online identification of
the source Thevenin parameters are presented. This methodology is used to identify
reconnaissance activity on the normally-open switches in the substation, initiated
by attackers to gauge its controllability over the cyber network. The applications
of this methodology in monitoring the voltage stability of the grid is also discussed.
In the second part of this chapter (sections 4.3-4.5), we investigate the localization
of faults. Since the number of PMU sensors available to carry out the inference
is insufficient to ensure observability, the problem can be viewed as that of under-sampling
a "graph signal"; the analysis leads to a PMU placement strategy that can
achieve the highest resolution in localizing the fault, for a given number of sensors.
In both cases, the results of the analysis are leveraged in the detection of cyber-physical
attacks, where microPMU data and relevant SCADA network traffic information
are compared to determine if a network breach has affected the integrity of the system
information and/or operations.
In second part of this thesis (Part II), the security analysis considers the adequacy
and reliability of schedules for the gas and power network. The motivation for
scheduling jointly supply in gas and power networks is motivated by the increasing
reliance of power grids on natural gas generators (and, indirectly, on gas pipelines)
as providing critical reserves. Chapter 5 focuses on unveiling the challenges and
providing solution to this problem.
This research presents three topology control (corrective transmission switching) methodologies along with the detailed formulation of robust corrective switching. The robust model can be solved off-line to suggest switching actions that can be used in a dynamic security assessment tool in real-time. The proposed robust topology control algorithm can also generate multiple corrective switching actions for a particular contingency. The solution obtained from the robust topology control algorithm is guaranteed to be feasible for the entire uncertainty set, i.e., a range of system operating states.
Furthermore, this research extends the benefits of robust corrective topology control to renewable resource integration. In recent years, the penetration of renewable resources in electrical power systems has increased. These renewable resources add more complexities to power system operations, due to their intermittent nature. This research presents robust corrective topology control as a congestion management tool to manage power flows and the associated renewable uncertainty. The proposed day-ahead method determines the maximum uncertainty in renewable resources in terms of do-not-exceed limits combined with corrective topology control. The results obtained from the topology control algorithm are tested for system stability and AC feasibility.
The scalability of do-not-exceed limits problem, from a smaller test case to a realistic test case, is also addressed in this research. The do-not-exceed limit problem is simplified by proposing a zonal do-not-exceed limit formulation over a detailed nodal do-not-exceed limit formulation. The simulation results show that the zonal approach is capable of addressing scalability of the do-not-exceed limit problem for a realistic test case.
Lossy compression is a form of compression that slightly degrades a signal in ways that are ideally not detectable to the human ear. This is opposite to lossless compression, in which the sample is not degraded at all. While lossless compression may seem like the best option, lossy compression, which is used in most audio and video, reduces transmission time and results in much smaller file sizes. However, this compression can affect quality if it goes too far. The more compression there is on a waveform, the more degradation there is, and once a file is lossy compressed, this process is not reversible. This project will observe the degradation of an audio signal after the application of Singular Value Decomposition compression, a lossy compression that eliminates singular values from a signal’s matrix.