Prior work in literature has illustrated the benefits of using surge arrester as a way to improve the lighting performance of the substation and transmission line. Installing surge arresters would enhance the system reliability but it comes with an extra capital expenditure. This thesis provides simulation analysis to examine substation-specific

Prior work in literature has illustrated the benefits of using surge arrester as a way to improve the lighting performance of the substation and transmission line. Installing surge arresters would enhance the system reliability but it comes with an extra capital expenditure. This thesis provides simulation analysis to examine substation-specific applications of surge arrester as a way of determining the optimal, cost-effective placement of surge arresters. Four different surge arrester installation configurations are examined for the 500/230 kV Rudd substation which belongs to the utility, Salt River Project (SRP). The most efficient configuration is identified in this thesis. A new method “voltage-distance curve” is proposed in this work to evaluate different surge arrester installation configurations. Simulation results show that surge arresters only need to be equipped on certain location of the substation and can still ensure sufficient lightning protection.

With lower tower footing resistance, the lightning performance of the transmission line can typically be improved. However, when surge arresters are installed in the system, the footing resistance may have either negative or positive effect on the lightning performance. Different situations for both effects are studied in this thesis.

This thesis proposes a surge arrester installation strategy for the overhead transmission line lightning protection. In order to determine the most efficient surge arrester configuration of transmission line, the entire transmission line is divided into several line sections according to the footing resistance of its towers. A line section consists of the towers which have similar footing resistance. Two different designs are considered for transmission line lightning protection, they include: equip different number of surge arrester on selected phase of every tower, equip surge arresters on all phases of selected towers. By varying the number of the towers or the number of phases needs to be equipped with surge arresters, the threshold voltage for line insulator flashover is used to evaluate different surge arrester installation configurations. The way to determine the optimal surge arresters configuration for each line section is then introduced in this thesis.
ContributorsXia, Qianxue (Author) / Karady, George G. (Thesis advisor) / Ayyanar, Raja (Committee member) / Lei, Qin (Committee member) / Arizona State University (Publisher)
Created2018
156715-Thumbnail Image.png
Description
With the growing penetration of plug-in electric vehicles (PEVs), the impact of the PEV charging brought to the utility grid draws more and more attention. This thesis focused on the optimization of a home energy management system (HEMS) with the presence of PEVs. For a household microgrid with photovoltaic (PV)

With the growing penetration of plug-in electric vehicles (PEVs), the impact of the PEV charging brought to the utility grid draws more and more attention. This thesis focused on the optimization of a home energy management system (HEMS) with the presence of PEVs. For a household microgrid with photovoltaic (PV) panels and PEVs, a HEMS using model predictive control (MPC) is designed to achieve the optimal PEV charging. Soft electric loads and an energy storage system (ESS) are also considered in the optimization of PEV charging in the MPC framework. The MPC is solved through mixed-integer linear programming (MILP) by considering the relationship of energy flows in the optimization problem. Through the simulation results, the performance of optimization results under various electricity price plans is evaluated. The influences of PV capacities on the optimization results of electricity cost are also discussed. Furthermore, the hardware development of a microgrid prototype is also described in this thesis.
ContributorsZhao, Yue (Author) / Chen, Yan (Thesis advisor) / Johnson, Nathan (Committee member) / Lei, Qin (Committee member) / Arizona State University (Publisher)
Created2018
156981-Thumbnail Image.png
Description
Switching surges are a common type of phenomenon that occur on any sort of power system network. These are more pronounced on long transmission lines and in high voltage substations. The problem with switching surges is encountered when a lot of power is transmitted across a transmission line
etwork, typically from

Switching surges are a common type of phenomenon that occur on any sort of power system network. These are more pronounced on long transmission lines and in high voltage substations. The problem with switching surges is encountered when a lot of power is transmitted across a transmission line
etwork, typically from a concentrated generation node to a concentrated load. The problem becomes significantly worse when the transmission line is long and when the voltage levels are high, typically above 400 kV. These overvoltage transients occur following any type of switching action such as breaker operation, fault occurrence/clearance and energization, and they pose a very real danger to weakly interconnected systems. At EHV levels, the insulation coordination of such lines is mainly dictated by the peak level of switching surges, the most dangerous of which include three phase line energization and single-phase reclosing. Switching surges can depend on a number of independent and inter-dependent factors like voltage level, line length, tower construction, location along the line, and presence of other equipment like shunt/series reactors and capacitors.

This project discusses the approaches taken and methods applied to observe and tackle the problems associated with switching surges on a long transmission line. A detailed discussion pertaining to different aspects of switching surges and their effects is presented with results from various studies published in IEEE journals and conference papers. Then a series of simulations are presented to determine an arrangement of substation equipment with respect to incoming transmission lines; that correspond to the lowest surge levels at that substation.
ContributorsShaikh, Mohammed Mubashir (Author) / Qin, Jiangchao (Thesis advisor) / Heydt, Gerald T (Committee member) / Lei, Qin (Committee member) / Arizona State University (Publisher)
Created2018
157844-Thumbnail Image.png
Description
This dissertation covers three primary topics and relates them in context. High frequency transformer design, microgrid modeling and control, and converter design as it pertains to the other topics are each investigated, establishing a summary of the state-of-the-art at the intersection of the three as a baseline. The culminating work

This dissertation covers three primary topics and relates them in context. High frequency transformer design, microgrid modeling and control, and converter design as it pertains to the other topics are each investigated, establishing a summary of the state-of-the-art at the intersection of the three as a baseline. The culminating work produced by the confluence of these topics is a novel modular solid-state transformer (SST) design, featuring an array of dual active bridge (DAB) converters, each of which contains an optimized high-frequency transformer, and an array of grid-forming inverters (GFI) suitable for centralized control in a microgrid environment. While no hardware was produced for this design, detailed modeling and simulation has been completed, and results are contextualized by rigorous analysis and comparison with results from published literature. The main contributions to each topic are best presented by topic area. For transformers, contributions include collation and presentation of the best-known methods of minimum loss high-frequency transformer design and analysis, descriptions of the implementation of these methods into a unified design script as well as access to an example of such a script, and the derivation and presentation of novel tools for analysis of multi-winding and multi-frequency transformers. For microgrid modeling and control, contributions include the modeling and simulation validation of the GFI and SST designs via state space modeling in a multi-scale simulation framework, as well as demonstration of stable and effective participation of these models in a centralized control scheme under phase imbalance. For converters, the SST design, analysis, and simulation are the primary contributions, though several novel derivations and analysis tools are also presented for the asymmetric half bridge and DAB.
ContributorsMongrain, Robert Scott (Author) / Ayyanar, Raja (Thesis advisor) / Pan, George (Committee member) / Qin, Jiangchao (Committee member) / Lei, Qin (Committee member) / Arizona State University (Publisher)