Matching Items (4)
Filtering by

Clear all filters

151994-Thumbnail Image.png
Description
Under the framework of intelligent management of power grids by leveraging advanced information, communication and control technologies, a primary objective of this study is to develop novel data mining and data processing schemes for several critical applications that can enhance the reliability of power systems. Specifically, this study is broadly

Under the framework of intelligent management of power grids by leveraging advanced information, communication and control technologies, a primary objective of this study is to develop novel data mining and data processing schemes for several critical applications that can enhance the reliability of power systems. Specifically, this study is broadly organized into the following two parts: I) spatio-temporal wind power analysis for wind generation forecast and integration, and II) data mining and information fusion of synchrophasor measurements toward secure power grids. Part I is centered around wind power generation forecast and integration. First, a spatio-temporal analysis approach for short-term wind farm generation forecasting is proposed. Specifically, using extensive measurement data from an actual wind farm, the probability distribution and the level crossing rate of wind farm generation are characterized using tools from graphical learning and time-series analysis. Built on these spatial and temporal characterizations, finite state Markov chain models are developed, and a point forecast of wind farm generation is derived using the Markov chains. Then, multi-timescale scheduling and dispatch with stochastic wind generation and opportunistic demand response is investigated. Part II focuses on incorporating the emerging synchrophasor technology into the security assessment and the post-disturbance fault diagnosis of power systems. First, a data-mining framework is developed for on-line dynamic security assessment by using adaptive ensemble decision tree learning of real-time synchrophasor measurements. Under this framework, novel on-line dynamic security assessment schemes are devised, aiming to handle various factors (including variations of operating conditions, forced system topology change, and loss of critical synchrophasor measurements) that can have significant impact on the performance of conventional data-mining based on-line DSA schemes. Then, in the context of post-disturbance analysis, fault detection and localization of line outage is investigated using a dependency graph approach. It is shown that a dependency graph for voltage phase angles can be built according to the interconnection structure of power system, and line outage events can be detected and localized through networked data fusion of the synchrophasor measurements collected from multiple locations of power grids. Along a more practical avenue, a decentralized networked data fusion scheme is proposed for efficient fault detection and localization.
ContributorsHe, Miao (Author) / Zhang, Junshan (Thesis advisor) / Vittal, Vijay (Thesis advisor) / Hedman, Kory (Committee member) / Si, Jennie (Committee member) / Ye, Jieping (Committee member) / Arizona State University (Publisher)
Created2013
149934-Thumbnail Image.png
Description
This research work describes the design of a fault current limiter (FCL) using digital logic and a microcontroller based data acquisition system for an ultra fast pilot protection system. These systems have been designed according to the requirements of the Future Renewable Electric Energy Delivery and Management (FREEDM) system (or

This research work describes the design of a fault current limiter (FCL) using digital logic and a microcontroller based data acquisition system for an ultra fast pilot protection system. These systems have been designed according to the requirements of the Future Renewable Electric Energy Delivery and Management (FREEDM) system (or loop), a 1 MW green energy hub. The FREEDM loop merges advanced power electronics technology with information tech-nology to form an efficient power grid that can be integrated with the existing power system. With the addition of loads to the FREEDM system, the level of fault current rises because of increased energy flow to supply the loads, and this requires the design of a limiter which can limit this current to a level which the existing switchgear can interrupt. The FCL limits the fault current to around three times the rated current. Fast switching Insulated-gate bipolar transistor (IGBT) with its gate control logic implements a switching strategy which enables this operation. A complete simulation of the system was built on Simulink and it was verified that the FCL limits the fault current to 1000 A compared to more than 3000 A fault current in the non-existence of a FCL. This setting is made user-defined. In FREEDM system, there is a need to interrupt a fault faster or make intelligent deci-sions relating to fault events, to ensure maximum availability of power to the loads connected to the system. This necessitates fast acquisition of data which is performed by the designed data acquisition system. The microcontroller acquires the data from a current transformer (CT). Mea-surements are made at different points in the FREEDM system and merged together, to input it to the intelligent protection algorithm that has been developed by another student on the project. The algorithm will generate a tripping signal in the event of a fault. The developed hardware and the programmed software to accomplish data acquisition and transmission are presented here. The designed FCL ensures that the existing switchgear equipments need not be replaced thus aiding future power system expansion. The developed data acquisition system enables fast fault sensing in protection schemes improving its reliability.
ContributorsThirumalai, Arvind (Author) / Karady, George G. (Thesis advisor) / Vittal, Vijay (Committee member) / Hedman, Kory (Committee member) / Arizona State University (Publisher)
Created2011
154077-Thumbnail Image.png
Description
ABSTRACT

This dissertation introduces a real-time topology monitoring scheme for power systems intended to provide enhanced situational awareness during major system disturbances. The topology monitoring scheme requires accurate real-time topology information to be effective. This scheme is supported by advances in transmission line outage detection based on data-mining phasor measurement unit

ABSTRACT

This dissertation introduces a real-time topology monitoring scheme for power systems intended to provide enhanced situational awareness during major system disturbances. The topology monitoring scheme requires accurate real-time topology information to be effective. This scheme is supported by advances in transmission line outage detection based on data-mining phasor measurement unit (PMU) measurements.

A network flow analysis scheme is proposed to track changes in user defined minimal cut sets within the system. This work introduces a new algorithm used to update a previous network flow solution after the loss of a single system branch. The proposed new algorithm provides a significantly decreased solution time that is desired in a real- time environment. This method of topology monitoring can provide system operators with visual indications of potential problems in the system caused by changes in topology.

This work also presents a method of determining all singleton cut sets within a given network topology called the one line remaining (OLR) algorithm. During operation, if a singleton cut set exists, then the system cannot withstand the loss of any one line and still remain connected. The OLR algorithm activates after the loss of a transmission line and determines if any singleton cut sets were created. These cut sets are found using properties of power transfer distribution factors and minimal cut sets.

The topology analysis algorithms proposed in this work are supported by line outage detection using PMU measurements aimed at providing accurate real-time topology information. This process uses a decision tree (DT) based data-mining approach to characterize a lost tie line in simulation. The trained DT is then used to analyze PMU measurements to detect line outages. The trained decision tree was applied to real PMU measurements to detect the loss of a 500 kV line and had no misclassifications.

The work presented has the objective of enhancing situational awareness during significant system disturbances in real time. This dissertation presents all parts of the proposed topology monitoring scheme and justifies and validates the methodology using a real system event.
ContributorsWerho, Trevor Nelson (Author) / Vittal, Vijay (Thesis advisor) / Heydt, Gerald (Committee member) / Hedman, Kory (Committee member) / Karady, George G. (Committee member) / Arizona State University (Publisher)
Created2015
155233-Thumbnail Image.png
Description
The power system is the largest man-made physical network in the world. Performing analysis of a large bulk system is computationally complex, especially when the study involves engineering, economic and environmental considerations. For instance, running a unit-commitment (UC) over a large system involves a huge number of constraints and integer

The power system is the largest man-made physical network in the world. Performing analysis of a large bulk system is computationally complex, especially when the study involves engineering, economic and environmental considerations. For instance, running a unit-commitment (UC) over a large system involves a huge number of constraints and integer variables. One way to reduce the computational expense is to perform the analysis on a small equivalent (reduced) model instead on the original (full) model.

The research reported here focuses on improving the network reduction methods so that the calculated results obtained from the reduced model better approximate the performance of the original model. An optimization-based Ward reduction (OP-Ward) and two new generator placement methods in network reduction are introduced and numerical test results on large systems provide proof of concept.

In addition to dc-type reductions (ignoring reactive power, resistance elements in the network, etc.), the new methods applicable to ac domain are introduced. For conventional reduction methods (Ward-type methods, REI-type methods), eliminating external generator buses (PV buses) is a tough problem, because it is difficult to accurately approximate the external reactive support in the reduced model. Recently, the holomorphic embedding (HE) based load-flow method (HELM) was proposed, which theoretically guarantees convergence given that the power flow equations are structure in accordance with Stahl’s theory requirements. In this work, a holomorphic embedding based network reduction (HE reduction) method is proposed which takes advantage of the HELM technique. Test results shows that the HE reduction method can approximate the original system performance very accurately even when the operating condition changes.
ContributorsZhu, Yujia (Author) / Tylavsky, Daniel John (Thesis advisor) / Vittal, Vijay (Committee member) / Hedman, Kory (Committee member) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2017