Matching Items (88)
Filtering by

Clear all filters

156071-Thumbnail Image.png
Description
The flexibility in power system networks is not fully modeled in existing real-time contingency analysis (RTCA) and real-time security-constrained economic dispatch (RT SCED) applications. Thus, corrective transmission switching (CTS) is proposed in this dissertation to enable RTCA and RT SCED to take advantage of the flexibility in the transmission system

The flexibility in power system networks is not fully modeled in existing real-time contingency analysis (RTCA) and real-time security-constrained economic dispatch (RT SCED) applications. Thus, corrective transmission switching (CTS) is proposed in this dissertation to enable RTCA and RT SCED to take advantage of the flexibility in the transmission system in a practical way.

RTCA is first conducted to identify critical contingencies that may cause violations. Then, for each critical contingency, CTS is performed to determine the beneficial switching actions that can reduce post-contingency violations. To reduce computational burden, fast heuristic algorithms are proposed to generate candidate switching lists. Numerical simulations performed on three large-scale realistic power systems (TVA, ERCOT, and PJM) demonstrate that CTS can significantly reduce post-contingency violations. Parallel computing can further reduce the solution time.

RT SCED is to eliminate the actual overloads and potential post-contingency overloads identified by RTCA. Procedure-A, which is consistent with existing industry practices, is proposed to connect RTCA and RT SCED. As CTS can reduce post-contingency violations, higher branch limits, referred to as pseudo limits, may be available for some contingency-case network constraints. Thus, Procedure-B is proposed to take advantage of the reliability benefits provided by CTS. With the proposed Procedure-B, CTS can be modeled in RT SCED implicitly through the proposed pseudo limits for contingency-case network constraints, which requires no change to existing RT SCED tools. Numerical simulations demonstrate that the proposed Procedure-A can effectively eliminate the flow violations reported by RTCA and that the proposed Procedure-B can reduce most of the congestion cost with consideration of CTS.

The system status may be inaccurately estimated due to false data injection (FDI) cyber-attacks, which may mislead operators to adjust the system improperly and cause network violations. Thus, a two-stage FDI detection (FDID) approach, along with several metrics and an alert system, is proposed in this dissertation to detect FDI attacks. The first stage is to determine whether the system is under attack and the second stage would identify the target branch. Numerical simulations demonstrate the effectiveness of the proposed two-stage FDID approach.
ContributorsLi, Xingpeng (Author) / Hedman, Kory (Thesis advisor) / Heydt, Gerald (Committee member) / Vittal, Vijay (Committee member) / Qin, Jiangchao (Committee member) / Arizona State University (Publisher)
Created2017
158716-Thumbnail Image.png
Description
The availability of data for monitoring and controlling the electrical grid has increased exponentially over the years in both resolution and quantity leaving a large data footprint. This dissertation is motivated by the need for equivalent representations of grid data in lower-dimensional feature spaces so that

The availability of data for monitoring and controlling the electrical grid has increased exponentially over the years in both resolution and quantity leaving a large data footprint. This dissertation is motivated by the need for equivalent representations of grid data in lower-dimensional feature spaces so that machine learning algorithms can be employed for a variety of purposes. To achieve that, without sacrificing the interpretation of the results, the dissertation leverages the physics behind power systems, well-known laws that underlie this man-made infrastructure, and the nature of the underlying stochastic phenomena that define the system operating conditions as the backbone for modeling data from the grid.

The first part of the dissertation introduces a new framework of graph signal processing (GSP) for the power grid, Grid-GSP, and applies it to voltage phasor measurements that characterize the overall system state of the power grid. Concepts from GSP are used in conjunction with known power system models in order to highlight the low-dimensional structure in data and present generative models for voltage phasors measurements. Applications such as identification of graphical communities, network inference, interpolation of missing data, detection of false data injection attacks and data compression are explored wherein Grid-GSP based generative models are used.

The second part of the dissertation develops a model for a joint statistical description of solar photo-voltaic (PV) power and the outdoor temperature which can lead to better management of power generation resources so that electricity demand such as air conditioning and supply from solar power are always matched in the face of stochasticity. The low-rank structure inherent in solar PV power data is used for forecasting and to detect partial-shading type of faults in solar panels.
ContributorsRamakrishna, Raksha (Author) / Scaglione, Anna (Thesis advisor) / Cochran, Douglas (Committee member) / Spanias, Andreas (Committee member) / Vittal, Vijay (Committee member) / Zhang, Junshan (Committee member) / Arizona State University (Publisher)
Created2020
158236-Thumbnail Image.png
Description
Power systems are undergoing a significant transformation as a result of the retirements of conventional coal-fired generation units and the increasing integration of converter interfaced renewable resources. The instantaneous renewable generation penetration as a percentage of the load served in megawatt (MW), in some areas of the United States (U.S.)

Power systems are undergoing a significant transformation as a result of the retirements of conventional coal-fired generation units and the increasing integration of converter interfaced renewable resources. The instantaneous renewable generation penetration as a percentage of the load served in megawatt (MW), in some areas of the United States (U.S.) sometimes approaches over 50 percent. These changes have introduced new challenges for reliability studies considering the two functional reliability aspects, i.e., adequacy and the dynamic security or operating reliability.

Adequacy assessment becomes more complex due to the variability introduced by renewable energy generation. The traditionally used reserve margin only considers projected peak demand and would be inadequate since it does not consider an evaluation of off-peak conditions that could also be critical due to the variable renewable generation. Therefore, in order to address the impact of variable renewable generation, a probabilistic evaluation that studies all hours of a year based on statistical characteristics is a necessity to identify the adequacy risks. On the other hand, the system dynamic behavior is also changing. Converter interfaced generation resources have different dynamic characteristics from the conventional synchronous units and inherently do not participate in grid regulation functions such as frequency control and voltage control that are vital to maintaining operating reliability. In order to evaluate these evolving grid characteristics, comprehensive reliability evaluation approaches that consider system stochasticity and evaluate both adequacy and dynamic security are important to identify potential system risks in this transforming environment.
ContributorsWang, Yingying (Author) / Vittal, Vijay (Thesis advisor) / Khorsand, Mojdeh (Thesis advisor) / Heydt, Gerald (Committee member) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2020
157883-Thumbnail Image.png
Description
In recent years, with the increasing penetration of solar generation, the uncertainty and variability of the power system generation also have increased. Power systems always require a balance between generation and load. The generation of the conventional generators must be scheduled to meet the total net load of the system

In recent years, with the increasing penetration of solar generation, the uncertainty and variability of the power system generation also have increased. Power systems always require a balance between generation and load. The generation of the conventional generators must be scheduled to meet the total net load of the system with the variability and uncertainty of the solar resources integrated. The ability to match generation to load requires certain flexibility of the conventional generation units as well as a flexible transmission network to deliver the power. In this work, given the generation flexibility primarily reflected in the ramping rates, as well as the minimum and maximum output of the generation units, the transmission network flexibility is assessed using the metric developed in this work.

The main topic of this thesis is the examination of the transmission system flexibility using time series power flows (TSPFs). First, a TSPFs program is developed considering the economic dispatch of all the generating stations, as well as the available ramping rate of each generating unit. The time series power flow spans a period of 24 hours with 5-minute time interval and hence includes 288 power flow snapshots. Every power flow snapshot is created based on the power system topology and the previous system state. These power flow snapshots are referred to as the base case power flow below.

Sensitivity analysis is then conducted by using the TSPFs program as a primary tool, by fixing all but one of the system changes which include: solar penetration, wires to wires interconnection, expected retirements of coal units and expected participation in the energy

imbalance market. The impact of each individual change can be evaluated by the metric developed in the following chapters.
ContributorsChen, Mengxi (Author) / Vittal, Vijay (Thesis advisor) / Hedman, Mojdeh Khorsand (Committee member) / Wu, Meng (Committee member) / Arizona State University (Publisher)
Created2019
157917-Thumbnail Image.png
Description
The grand transition of electric grids from conventional fossil fuel resources to intermittent bulk renewable resources and distributed energy resources (DERs) has initiated a paradigm shift in power system operation. Distributed energy resources (i.e. rooftop solar photovoltaic, battery storage, electric vehicles, and demand response), communication infrastructures, and smart measurement devices

The grand transition of electric grids from conventional fossil fuel resources to intermittent bulk renewable resources and distributed energy resources (DERs) has initiated a paradigm shift in power system operation. Distributed energy resources (i.e. rooftop solar photovoltaic, battery storage, electric vehicles, and demand response), communication infrastructures, and smart measurement devices provide the opportunity for electric utility customers to play an active role in power system operation and even benefit financially from this opportunity. However, new operational challenges have been introduced due to the intrinsic characteristics of DERs such as intermittency of renewable resources, distributed nature of these resources, variety of DERs technologies and human-in-the-loop effect. Demand response (DR) is one of DERs and is highly influenced by human-in-the-loop effect. A data-driven based analysis is implemented to analyze and reveal the customers price responsiveness, and human-in-the-loop effect. The results confirm the critical impact of demographic characteristics of customers on their interaction with smart grid and their quality of service (QoS). The proposed framework is also applicable to other types of DERs. A chance-constraint based second-order-cone programming AC optimal power flow (SOCP-ACOPF) is utilized to dispatch DERs in distribution grid with knowing customers price responsiveness and energy output distribution. The simulation shows that the reliability of distribution gird can be improved by using chance-constraint.
ContributorsHe, Mingyue (Author) / Khorsand, Mojdeh (Thesis advisor) / Vittal, Vijay (Committee member) / Pal, Anamitra (Committee member) / Arizona State University (Publisher)
Created2019
158388-Thumbnail Image.png
Description
The electric power system (EPS) is an extremely complex system that has operational interdependencies with the water delivery and treatment system (WDTS). The term water-energy nexus is commonly used to describe the critical interdependencies that naturally exist between the EPS and water distribution systems (WDS). Presented in this work is

The electric power system (EPS) is an extremely complex system that has operational interdependencies with the water delivery and treatment system (WDTS). The term water-energy nexus is commonly used to describe the critical interdependencies that naturally exist between the EPS and water distribution systems (WDS). Presented in this work is a framework for simulating interactions between these two critical infrastructure systems in short-term and long-term time-scales. This includes appropriate mathematical models for system modeling and for optimizing control of power system operation with consideration of conditions in the WDS. Also presented is a complete methodology for quantifying the resilience of the two interdependent systems.

The key interdependencies between the two systems are the requirements of water for the cooling cycle of traditional thermal power plants as well as electricity for pumping and/or treatment in the WDS. While previous work has considered the dependency of thermoelectric generation on cooling water requirements at a high-level, this work considers the impact from limitations of cooling water into network simulations in both a short-term operational framework as well as in the long-term planning domain.

The work completed to set-up simulations in operational length time-scales was the development of a simulator that adequately models both systems. This simulation engine also facilitates the implementation of control schemes in both systems that take advantage of the knowledge of operating conditions in the other system. Initial steps for including the influence of anticipated water availability and water rights attainability within the combined generation and transmission expansion planning problem is also presented. Lastly, the framework for determining the infrastructural-operational resilience (IOR) of the interdependent systems is formulated.

Adequately modeling and studying the two systems and their interactions is becoming critically important. This importance is illustrated by the possibility of unforeseen natural or man-made events or by the likelihood of load increase in the systems, either of which has the risk of putting extreme stress on the systems beyond that experienced in normal operating conditions. Therefore, this work addresses these concerns with novel modeling and control/policy strategies designed to mitigate the severity of extreme conditions in either system.
ContributorsZuloaga, Scott (Author) / Vittal, Vijay (Thesis advisor) / Zhang, Junshan (Committee member) / Mays, Larry (Committee member) / Wu, Meng (Committee member) / Arizona State University (Publisher)
Created2020
153496-Thumbnail Image.png
Description
An important operating aspect of all transmission systems is power system stability

and satisfactory dynamic performance. The integration of renewable resources in general, and photovoltaic resources in particular into the grid has created new engineering issues. A particularly problematic operating scenario occurs when conventional generation is operated at a low level

An important operating aspect of all transmission systems is power system stability

and satisfactory dynamic performance. The integration of renewable resources in general, and photovoltaic resources in particular into the grid has created new engineering issues. A particularly problematic operating scenario occurs when conventional generation is operated at a low level but photovoltaic solar generation is at a high level. Significant solar photovoltaic penetration as a renewable resource is becoming a reality in some electric power systems. In this thesis, special attention is given to photovoltaic generation in an actual electric power system: increased solar penetration has resulted in significant strides towards meeting renewable portfolio standards. The impact of solar generation integration on power system dynamics is studied and evaluated.

This thesis presents the impact of high solar penetration resulting in potentially

problematic low system damping operating conditions. This is the case because the power system damping provided by conventional generation may be insufficient due to reduced system inertia and change in power flow patterns affecting synchronizing and damping capability in the AC system. This typically occurs because conventional generators are rescheduled or shut down to allow for the increased solar production. This problematic case may occur at any time of the year but during the springtime months of March-May, when the system load is low and the ambient temperature is relatively low, there is the potential that over voltages may occur in the high voltage transmission system. Also, reduced damping in system response to disturbances may occur. An actual case study is considered in which real operating system data are used. Solutions to low damping cases are discussed and a solution based on the retuning of a conventional power system stabilizer is given in the thesis.
ContributorsPethe, Anushree Sanjeev (Author) / Vittal, Vijay (Thesis advisor) / Heydt, Gerald T (Thesis advisor) / Ayyanar, Raja (Committee member) / Arizona State University (Publisher)
Created2015
154428-Thumbnail Image.png
Description
The grounding system in a substation is used to protect personnel and equipment. When there is fault current injected into the ground, a well-designed grounding system should disperse the fault current into the ground in order to limit the touch potential and the step potential to an acceptable level defined

The grounding system in a substation is used to protect personnel and equipment. When there is fault current injected into the ground, a well-designed grounding system should disperse the fault current into the ground in order to limit the touch potential and the step potential to an acceptable level defined by the IEEE Std 80. On the other hand, from the point of view of economy, it is desirable to design a ground grid that minimizes the cost of labor and material. To design such an optimal ground grid that meets the safety metrics and has the minimum cost, an optimal ground grid application was developed in MATLAB, the OptimaL Ground Grid Application (OLGGA).

In the process of ground grid optimization, the touch potential and the step potential are introduced as nonlinear constraints in a two layer soil model whose parameters are set by the user. To obtain an accurate expression for these nonlinear constraints, the ground grid is discretized by using a ground-conductor (and ground-rod) segmentation method that breaks each conductor into reasonable-size segments. The leakage current on each segment and the ground potential rise (GPR) are calculated by solving a matrix equation involving the mutual resistance matrix. After the leakage current on each segment is obtained, the touch potential and the step potential can be calculated using the superposition principle.

A genetic algorithm is used in the optimization of the ground grid and a pattern search algorithm is used to accelerate the convergence. To verify the accuracy of the application, the touch potential and the step potential calculated by the MATLAB application are compared with those calculated by the commercialized grounding system analysis software, WinIGS.

The user's manual of the optimal ground grid application is also presented in this work.
ContributorsLi, Songyan (Author) / Tylavsky, Daniel J. (Thesis advisor) / Ayyanar, Raja (Committee member) / Vittal, Vijay (Committee member) / Arizona State University (Publisher)
Created2016