Matching Items (59)
Filtering by

Clear all filters

149510-Thumbnail Image.png
Description
Optical Instrument Transformers (OIT) have been developed as an alternative to traditional instrument transformers (IT). The question "Can optical instrument transformers substitute for the traditional transformers?" is the main motivation of this study. Finding the answer for this question and developing complete models are the contributions of this work. Dedicated

Optical Instrument Transformers (OIT) have been developed as an alternative to traditional instrument transformers (IT). The question "Can optical instrument transformers substitute for the traditional transformers?" is the main motivation of this study. Finding the answer for this question and developing complete models are the contributions of this work. Dedicated test facilities are developed so that the steady state and transient performances of analog outputs of a magnetic current transformer (CT) and a magnetic voltage transformer (VT) are compared with that of an optical current transformer (OCT) and an optical voltage transformer (OVT) respectively. Frequency response characteristics of OIT outputs are obtained. Comparison results show that OITs have a specified accuracy of 0.3% in all cases. They are linear, and DC offset does not saturate the systems. The OIT output signal has a 40~60 μs time delay, but this is typically less than the equivalent phase difference permitted by the IEEE and IEC standards for protection applications. Analog outputs have significantly higher bandwidths (adjustable to 20 to 40 kHz) than the IT. The digital output signal bandwidth (2.4 kHz) of an OCT is significantly lower than the analog signal bandwidth (20 kHz) due to the sampling rates involved. The OIT analog outputs may have significant white noise of 6%, but the white noise does not affect accuracy or protection performance. Temperatures up to 50oC do not adversely affect the performance of the OITs. Three types of models are developed for analog outputs: analog, digital, and complete models. Well-known mathematical methods, such as network synthesis and Jones calculus methods are applied. The developed models are compared with experiment results and are verified with simulation programs. Results show less than 1.5% for OCT and 2% for OVT difference and that the developed models can be used for power system simulations and the method used for the development can be used to develop models for all other brands of optical systems. The communication and data transfer between the all-digital protection systems is investigated by developing a test facility for all digital protection systems. Test results show that different manufacturers' relays and transformers based on the IEC standard can serve the power system successfully.
ContributorsKucuksari, Sadik (Author) / Karady, George G. (Thesis advisor) / Heydt, Gerald T (Committee member) / Holbert, Keith E. (Committee member) / Ayyanar, Raja (Committee member) / Farmer, Richard (Committee member) / Arizona State University (Publisher)
Created2010
149306-Thumbnail Image.png
Description
Many methods have been proposed to estimate power system small signal stability, for either analysis or control, through identification of modal frequencies and their damping levels. Generally, estimation methods have been employed to assess small signal stability from collected field measurements. However, the challenge to using these methods in assessing

Many methods have been proposed to estimate power system small signal stability, for either analysis or control, through identification of modal frequencies and their damping levels. Generally, estimation methods have been employed to assess small signal stability from collected field measurements. However, the challenge to using these methods in assessing field measurements is their ability to accurately estimate stability in the presence of noise. In this thesis a new method is developed which estimates the modal content of simulated and actual field measurements using orthogonal polynomials and the results are compared to other commonly used estimators. This new method estimates oscillatory performance by fitting an associate Hermite polynomial to time domain data and extrapolating its spectrum to identify small signal power system frequencies. Once the frequencies are identified, damping assessment is performed using a modified sliding window technique with the use of linear prediction (LP). Once the entire assessment is complete the measurements can be judged to be stable or unstable. Collectively, this new technique is known as the associate Hermite expansion (AHE) algorithm. Validation of the AHE method versus results from four other spectral estimators demonstrates the method's accuracy and modal estimation ability with and without the presence of noise. A Prony analysis, a Yule-Walker autoregressive algorithm, a second sliding window estimator and the Hilbert-Huang Transform method are used in comparative assessments in support of this thesis. Results from simulated and actual field measurements are used in the comparisons, as well as artificially generated simple signals. A search for actual field testing results performed by a utility was undertaken and a request was made to obtain the measurements of a brake insertion test. Comparison results show that the AHE method is accurate as compared to the other commonly used spectral estimators and its predictive capability exceeded the other estimators in the presence of Gaussian noise. As a result, the AHE method could be employed in areas including operations and planning analysis, post-mortem analysis, power system damping scheme design and other analysis areas.
ContributorsKokanos, Barrie Lee (Author) / Karady, George G. (Thesis advisor) / Heydt, Gerald (Committee member) / Farmer, Richard G (Committee member) / Ayyanar, Raja (Committee member) / Karam, Lina (Committee member) / Arizona State University (Publisher)
Created2010
187826-Thumbnail Image.png
Description
There has been a significant growth in the distributed energy resources (DERs) connected to the distribution networks in recent years. For a distribution system with a high penetration of DERs, a detailed modeling and representation of the distribution network is needed to accurately assess its steady-state and dynamic behavior. In

There has been a significant growth in the distributed energy resources (DERs) connected to the distribution networks in recent years. For a distribution system with a high penetration of DERs, a detailed modeling and representation of the distribution network is needed to accurately assess its steady-state and dynamic behavior. In this dissertation, a field-validated model for a real sub-transmission and distribution network is developed, including one of the feeders modeled with the secondary network and loads and solar PV units at their household/user location. A procedure is developed combining data from various sources such as the utility database, geoinformation data, and field measurements to create an accurate network model. Applying a single line to ground fault to the detailed distribution feeder model, a high voltage swell, with potentially detrimental impacts on connected equipment, is shown in one of the non-faulted phases of the feeder. The reason for this voltage swell is analyzed in detail. It is found that with appropriate control the solar PV units on the feeder can reduce the severity of the voltage swell, but not entirely eliminate it. For integrated studies of the transmission-distribution (T&D) network, a T&D co-simulation framework is developed, which is capable of power flow as well as dynamic simulations, and supports unbalanced modeling and disturbances in the distribution as well as the sub-transmission system. The power flow co-simulation framework is developed as a module that can be run on a cloud-based platform. Using the developed framework, the T&D system response is studied for balanced and unbalanced faults on the distribution and sub-transmission system. For some faults the resultant loss of generation can potentially lead to the entire feeder tripping due to high unbalance at the substation. However, it is found that advanced inverter controls may improve the response of the distribution feeders to the faults. The dissertation also highlights the importance of modeling the secondary network for both steady-state and dynamic studies. Lastly, a preliminary investigation is conducted to include different dynamic elements such as grid-forming inverters in a T&D network simulation.
ContributorsThakar, Sushrut (Author) / Vittal, Vijay (Thesis advisor) / Ayyanar, Raja (Thesis advisor) / Hedman, Mojdeh (Committee member) / Ramapuram Matavalam, Amarsagar Reddy (Committee member) / Arizona State University (Publisher)
Created2023
171672-Thumbnail Image.png
Description
Voltage Source Inverter (VSI) is an integral component that converts DC voltage to AC voltage suitable for driving the electric motor in Electric Vehicles/Hybrid Electric Vehicles (EVs/HEVs) and integration with electric grid in grid-connected photovoltaic (PV) converter. Performance of VSI is significantly impacted by the type of Pulse Width Modulation

Voltage Source Inverter (VSI) is an integral component that converts DC voltage to AC voltage suitable for driving the electric motor in Electric Vehicles/Hybrid Electric Vehicles (EVs/HEVs) and integration with electric grid in grid-connected photovoltaic (PV) converter. Performance of VSI is significantly impacted by the type of Pulse Width Modulation (PWM) method used.In this work, a new PWM method called 240° Clamped Space Vector PWM (240CPWM) is studied extensively. 240CPWM method has the major advantages of clamping a phase to the positive or negative rail for 240° in a fundamental period, clamping of two phases simultaneously at any given instant, and use of only active states, completely eliminating the zero states. These characteristics lead to a significant reduction in switching losses of the inverter and lower DC link capacitor current stress as compared to Conventional Space Vector PWM. A unique six pulse dynamically varying DC link voltage is required for 240CPWM instead of constant DC link voltage to maintain sinusoidal output voltage. Voltage mode control of DC-DC stage with Smith predictor is developed for shaping the dynamic DC link voltage that meets the requirements for fast control. Experimental results from a 10 kW hardware prototype with 10 kHz switching frequency validate the superior performance of 240CPWM in EV/HEV traction inverters focusing on loss reduction and DC link capacitor currents. Full load efficiency with the proposed 240CPWM for the DC-AC stage even with conventional Silicon devices exceeds 99%. Performance of 240CPWM is evaluated in three phase grid-connected PV converter. It is verified experimentally that 240CPWM performs well under adverse grid conditions like sag/swell and unbalance in grid voltages, and under a wide range of power factor. Undesired low frequency harmonics in inverter currents are minimized using the Harmonic Compensator that results in Total Harmonic Distortion (THD) of 3.5% with 240CPWM in compliance with grid interconnection standards. A new, combined performance index is proposed to compare the performance of different PWM schemes in terms of switching loss, THD, DC link current stress, Common Mode Voltage and leakage current. 240CPWM achieves the best value for this index among the PWM methods studied.
ContributorsQamar, Haleema (Author) / Ayyanar, Raja (Thesis advisor) / Yu, Hongbin (Committee member) / Lei, Qin (Committee member) / Weng, Yang (Committee member) / Arizona State University (Publisher)
Created2022
187366-Thumbnail Image.png
Description
The high R/X ratio of typical distribution systems makes the system voltage vulnerable to active power injection from the distributed energy resources (DERs). Moreover, the intermittent and uncertain nature of the DER generation brings new challenges to voltage management. As guided by the previous IEEE standard 1547-2003, most of the

The high R/X ratio of typical distribution systems makes the system voltage vulnerable to active power injection from the distributed energy resources (DERs). Moreover, the intermittent and uncertain nature of the DER generation brings new challenges to voltage management. As guided by the previous IEEE standard 1547-2003, most of the existing photovoltaic (PV) systems in the real distribution networks are equipped with conventional inverters, which only allow the PV systems to operate at unity power factor to generate active power. To utilize the voltage control capability of the existing PV systems following the guideline of the revised IEEE standard 1547-2018, this dissertation proposes a two-stage stochastic optimization strategy aimed at optimally placing the PV smart inverters with Volt-VAr capability among the existing PV systems for distribution systems with high PV penetration to mitigate voltage violations. PV smart inverters are fast-response devices compared to conventional voltage control devices in the distribution system. Historically, distribution system planning and operation studies are mainly based on quasi-static simulation, which ignores system dynamic transitions between static solutions. However, as high-penetration PV systems are present in the distribution system, the fast transients of the PV smart inverters cannot be ignored. A detailed dynamic model of the PV smart inverter with Volt-VAr control capability is developed as a dynamic link library (DLL) in OpenDSS to validate the system voltage stability with autonomous control of the optimally placed PV smart inverters. Static and dynamic verification is conducted on an actual 12.47 kV, 9 km-long Arizona utility feeder that serves residential customers. To achieve fast simulation and accommodate more complex PV models with desired accuracy and efficiency, an integrative dynamic simulation framework for OpenDSS with adaptive step size control is proposed. Based on the original fixed-step size simulation framework in OpenDSS, the proposed framework adds a function in the OpenDSS main program to adjust its step size to meet the minimum step size requirement from all the PV inverters in the system. Simulations are conducted using both the original and the proposed framework to validate the proposed simulation framework.
ContributorsChen, Mengxi (Author) / Vittal, Vijay (Thesis advisor) / Ayyanar, Raja (Thesis advisor) / Hedman, Mojdeh (Committee member) / Wu, Meng (Committee member) / Arizona State University (Publisher)
Created2023
171852-Thumbnail Image.png
Description
The past few years have witnessed a significant growth of distributed energy resources (DERs) in power systems at the customer level. Such growth challenges the traditional centralized model of conventional synchronous generation, making a transition to a decentralized network with a significant increase of DERs. This decentralized network requires a

The past few years have witnessed a significant growth of distributed energy resources (DERs) in power systems at the customer level. Such growth challenges the traditional centralized model of conventional synchronous generation, making a transition to a decentralized network with a significant increase of DERs. This decentralized network requires a paradigm change in modeling distribution systems in more detail to maintain the reliability and efficiency while accommodating a high level of DERs. Accurate models of distribution feeders, including the secondary network, loads, and DER components must be developed and validated for system planning and operation and to examine the distribution system performance. In this work, a detailed model of an actual feeder with high penetration of DERs from an electrical utility in Arizona is developed. For the primary circuit, distribution transformers, and cables are modeled. For the secondary circuit, actual conductors to each house, as well as loads and photovoltaic (PV) units at each premise are represented. An automated tool for secondary network topology construction for load feeder topology assignation is developed. The automated tool provides a more accurate feeder topology for power flow calculation purposes. The input data for this tool consists of parcel geographic information system (GIS) delimitation data, and utility secondary feeder topology database. Additionally, a highly automated, novel method to enhance the accuracy of utility distribution feeder models to capture their performance by matching simulation results with corresponding field measurements is presented. The method proposed uses advanced metering infrastructure (AMI) voltage and derived active power measurements at the customer level, data acquisition systems (DAS) measurements at the feeder-head, in conjunction with an AC optimal power flow (ACOPF) to estimate customer active and reactive power consumption over a time horizon, while accounting for unmetered loads. The method proposed estimates both voltage magnitude and angle for each phase at the unbalanced distribution substation. The accuracy of the method developed by comparing the time-series power flow results obtained from the enhancement algorithm with OpenDSS results and with the field measurements available. The proposed approach seamlessly manages the data available from the optimization procedure through the final model verification.
ContributorsMontano-Martinez, Karen Vanessa (Author) / Vittal, Vijay (Thesis advisor) / Ayyanar, Raja (Committee member) / Weng, Yang (Committee member) / Pal, Anamitra (Committee member) / Arizona State University (Publisher)
Created2022
171988-Thumbnail Image.png
Description
With the increasing penetration levels of distributed energy resources along distribution feeders, the importance of load modeling has grown significantly and therefore it is important to have an accurate representation of the distribution system in the planning and operation studies. Although, currently, most of the power system studies are being

With the increasing penetration levels of distributed energy resources along distribution feeders, the importance of load modeling has grown significantly and therefore it is important to have an accurate representation of the distribution system in the planning and operation studies. Although, currently, most of the power system studies are being done using positive sequence commercial software packages for computational convenience purposes, it comes at the cost of reduced accuracy when compared to the more accurate electromagnetic transient (EMT) simulators (but more computationally intensive). However, it is expected, that in the next several years, the use of EMT simulators for large-scale system studies would become a necessity to implement the ambitious renewable energy targets adopted by many countries across the world. Currently, the issue of developing more accurate EMT feeder and load models has yet to be addressed. Therefore, in the first phase of this work, an optimization algorithm to synthesize an EMT distribution feeder and load model has been developed by capturing the current transients when three-phase voltage measurements (obtained from a local utility) are played-in as input, from events such as sub-transmission faults, to the synthesized model. Using the developed algorithm, for the proposed feeder model, both the load composition and the load parameters have been estimated. The synthesized load model has a load composition which includes impedance loads, single-phase induction motor (SPHIM) loads and three-phase induction motor loads. In the second phase of this work, an analytical formulation of a 24 V EMT contactor is developed to trip the air conditioner EMT SPHIM load, in the feeder and load model developed in Phase 1 of this work, under low voltage conditions. Additionally, a new methodology is developed, to estimate and incorporate the trip and reconnection settings of the proposed EMT contactor model to trip, reconnect and stall the SPHIMs in a positive sequence simulator (PSLF) for single-line to ground faults. Also, the proposed methodology has been tested on a modified three-segment three-phase feeder model using a local utility’s practical feeder topological and loading information. Finally, the developed methodology is modified to accommodate three-phase faults in the system.
ContributorsNekkalapu, Sameer (Author) / Vittal, Vijay (Thesis advisor) / Undrill, John (Committee member) / Ayyanar, Raja (Committee member) / Wu, Meng (Committee member) / Arizona State University (Publisher)
Created2022
171384-Thumbnail Image.png
Description
Wide-BandGap (WBG) material-based switching devices such as gallium nitride (GaN) High Electron Mobility Transistors (HEMTs) and Silicon Carbide (SiC) Metal-Oxide-Semiconductor Field-Effect Transistors (MOSFETs) are considered very promising and valuable candidates for replacing conventional Silicon (Si) MOSFETs in various industrial high-frequency high-power applications, mainly because of their capabilities of higher switching

Wide-BandGap (WBG) material-based switching devices such as gallium nitride (GaN) High Electron Mobility Transistors (HEMTs) and Silicon Carbide (SiC) Metal-Oxide-Semiconductor Field-Effect Transistors (MOSFETs) are considered very promising and valuable candidates for replacing conventional Silicon (Si) MOSFETs in various industrial high-frequency high-power applications, mainly because of their capabilities of higher switching frequencies with less switching and conduction losses. However, to make the most of their advantages, it is crucial to understand the intrinsic differences between WBG-based and Si-based switching devices and investigate effective means to safely, efficiently, and reliably utilize the WBG devices. Firstly, a comprehensive understanding of traditional Modular Multilevel Converter (MMC) topology is presented. Different novel SubModule (SM) topologies are described in detail. The low frequency SM voltage fluctuation problem is also discussed. Based on the analysis, some novel topologies which manage to damp or eliminate the voltage ripple are illustrated in detail. As demonstrated, simulation results of these proposed topologies verify the theory. Moreover, the hardware design considerations of traditional MMC platform are discussed. Based on these, a 6 kW smart Modular Isolated Multilevel Converter (MIMC) with symmetrical resonant converter based Ripple current elimination channels is delivered and related experimental results further verify the effectiveness of proposed topology. Secondly, the evolution of GaN transistor structure, from classical normally-on device to normally-off GaN, is well-described. As the benefits, channel current capability and drain-source voltage are significantly boosted. However, accompanying the evolution of GaN devices, the dynamic on-resistance issue is one of the urgent problems to be solved since it strongly affects the GaN device current and voltage limit. Unlike traditional methods from the perspective of transistor structure, this report proposes a novel Multi-Level-Voltage-Output gate drive circuit (MVO-GD) aimed at alleviating the dynamic on-resistance issue from engineering point of view. The comparative tests of proposed MVO-GD and the standard 2-level gate driver (STD-GD) are conducted under variable test conditions which may affect dynamic on-resistance, such as drain-source voltage, gate current width, device package temperature and so on. The experimental waveforms and data have been demonstrated and analyzed.
ContributorsLIU, YIFU (Author) / Lei, Qin (Thesis advisor) / Ayyanar, Raja (Committee member) / Ranjram, Mike (Committee member) / Mallik, Ayan (Committee member) / Arizona State University (Publisher)
Created2022
171673-Thumbnail Image.png
Description
The performance of voltage source inverter (VSI) in terms of output waveform quality, conversion efficiency and common mode noise depends greatly on the pulse width modulation (PWM) method. In this work, a low-loss space vector PWM i.e., 240°-clamped space vector PWM (240CPWM) is proposed to improve the performance of VSIs

The performance of voltage source inverter (VSI) in terms of output waveform quality, conversion efficiency and common mode noise depends greatly on the pulse width modulation (PWM) method. In this work, a low-loss space vector PWM i.e., 240°-clamped space vector PWM (240CPWM) is proposed to improve the performance of VSIs in electric/hybrid electric vehicles (EV/HEVs) and grid connected photovoltaic (PV) systems. The salient features of 240CPWM include 240° clamping of each phase pole to positive or negative DC bus in a fundamental cycle ensuring that switching losses are reduced by a factor of seven as compared to conventional space vector PWM (CSVPWM) at unity power factor. Zero states are completely eliminated and only two nearest active states are used ensuring that there is no penalty in terms of total harmonic distortion (THD) in line current. The THD of the line current is analyzed using the notion of stator flux ripple and compared with conventional and discontinuous PWM method. Discontinuous PWM methods achieve switching loss reduction at the expense of higher THD while 240CPWM achieves a much greater loss reduction without impacting the THD. The analysis and performance of 240CPWM are validated on a 10 kW two-stage experimental prototype. Common mode voltage (CMV) and leakage current characteristics of 240CPWM are analyzed in detail. It is shown analytically that 240CPWM reduces the CMV and leakage current as compared to other PWM methods while simultaneously reducing the switching loss and THD. Experimental results from a 10-kW hardware prototype conform to the analytical discussions and validate the superior performance of 240CPWM. 240CPWM requires a six-pulse dynamic DC link voltage that introduces low frequency harmonics in DC input current and/or AC line currents that can affect maximum power point tracking, battery life or THD in line current. Four topologies have been proposed to minimize the low frequency harmonics in input and line currents in grid-connected PV system with 240CPWM. In order to achieve further benefits in terms of THD and device stress reduction, 240CPWM is extended to three-level inverters. The performance metrics such as THD and switching loss for 240CPWM are analyzed in three-level inverter.
ContributorsQamar, Hafsa (Author) / Ayyanar, Raja (Thesis advisor) / Yu, Hongbin (Committee member) / Lei, Qin (Committee member) / Weng, Yang (Committee member) / Arizona State University (Publisher)
Created2022
171708-Thumbnail Image.png
Description
Large number of renewable energy based distributed energy resources(DERs) are integrated into the conventional power grid using power electronic interfaces. This causes increased need for efficient power conversion, advanced control, and DER situational awareness. In case of photovoltaic(PV) grid integration, power is processed in two stages, namely DC-DC and DC-AC.

Large number of renewable energy based distributed energy resources(DERs) are integrated into the conventional power grid using power electronic interfaces. This causes increased need for efficient power conversion, advanced control, and DER situational awareness. In case of photovoltaic(PV) grid integration, power is processed in two stages, namely DC-DC and DC-AC. In this work, two novel soft-switching schemes for quadratic boost DC-DC converters are proposed for PV microinverter application. Both the schemes allow the converter to operate at higher switching frequency, reducing the converter size while still maintaining high power conversion efficiency. Further, to analyze the impact of high penetration DERs on the power system a real-time simulation platform has been developed in this work. A real, large distribution feeder with more than 8000 buses is considered for investigation. The practical challenges in the implementation of a real-time simulation (such as number of buses, simulation time step, and computational burden) and the corresponding solutions are discussed. The feeder under study has a large number of DERs leading to more than 200% instantaneous PV penetration. Opal-RT ePHASORSIM model of the distribution feeder and different types of DER models are discussed in detailed in this work. A novel DER-Edge-Cloud based three-level architecture is proposed for achieving solar situational awareness for the system operators and for real-time control of DERs. This is accomplished using a network of customized edge-intelligent-devices(EIDs) and end-to-end solar energy optimization platform(eSEOP). The proposed architecture attains superior data resolution, data transfer rate and low latency for the end-to-end communication. An advanced PV string inverter with control and communication capabilities exceeding those of state-of-the-art, commercial inverters has been developed to demonstrate the proposed real-time control. A power-hardware-in-loop(PHIL) and EID-in-loop(EIL) testbeds are developed to verify the impact of large number of controllable DERs on the distribution system under different operational modes such as volt-VAr, constant reactive power and constant power factor. Edge level data analytics and intelligent controls such as autonomous reactive power allocation strategy are implemented using EIL testbed for real-time monitoring and control. Finally, virtual oscillator control(VOC) for grid forming inverters and its operation under different X/R conditions are explored.
ContributorsKorada, Nikhil (Author) / Ayyanar, Raja (Thesis advisor) / Lei, Qin (Committee member) / Wu, Meng (Committee member) / Srinivasan, Devarajan (Committee member) / Arizona State University (Publisher)
Created2022