151100-Thumbnail Image.png
Description
The ability to shift the photovoltaic (PV) power curve and make the energy accessible during peak hours can be accomplished through pairing solar PV with energy storage technologies. A prototype hybrid air conditioning system (HACS), built under supervision of project head Patrick Phelan, consists of PV modules running a DC

The ability to shift the photovoltaic (PV) power curve and make the energy accessible during peak hours can be accomplished through pairing solar PV with energy storage technologies. A prototype hybrid air conditioning system (HACS), built under supervision of project head Patrick Phelan, consists of PV modules running a DC compressor that operates a conventional HVAC system paired with a second evaporator submerged within a thermal storage tank. The thermal storage is a 0.284m3 or 75 gallon freezer filled with Cryogel balls, submerged in a weak glycol solution. It is paired with its own separate air handler, circulating the glycol solution. The refrigerant flow is controlled by solenoid valves that are electrically connected to a high and low temperature thermostat. During daylight hours, the PV modules run the DC compressor. The refrigerant flow is directed to the conventional HVAC air handler when cooling is needed. Once the desired room temperature is met, refrigerant flow is diverted to the thermal storage, storing excess PV power. During peak energy demand hours, the system uses only small amounts of grid power to pump the glycol solution through the air handler (note the compressor is off), allowing for money and energy savings. The conventional HVAC unit can be scaled down, since during times of large cooling demands the glycol air handler can be operated in parallel with the conventional HVAC unit. Four major test scenarios were drawn up in order to fully comprehend the performance characteristics of the HACS. Upon initial running of the system, ice was produced and the thermal storage was charged. A simple test run consisting of discharging the thermal storage, initially ~¼ frozen, was performed. The glycol air handler ran for 6 hours and the initial cooling power was 4.5 kW. This initial test was significant, since greater than 3.5 kW of cooling power was produced for 3 hours, thus demonstrating the concept of energy storage and recovery.
ContributorsPeyton-Levine, Tobin (Author) / Phelan, Patrick (Thesis advisor) / Trimble, Steve (Committee member) / Wang, Robert (Committee member) / Arizona State University (Publisher)
Created2012
156483-Thumbnail Image.png
Description
The concept of this thesis came up as a part of the efforts being devoted around the world to reduce energy consumption, CO2 emissions, global warming and ozone layer depletion. In the United States, HVAC units in residential buildings consumed about 350 billion kWh in 2017 [1],[2]. Although HVAC manufacturers

The concept of this thesis came up as a part of the efforts being devoted around the world to reduce energy consumption, CO2 emissions, global warming and ozone layer depletion. In the United States, HVAC units in residential buildings consumed about 350 billion kWh in 2017 [1],[2]. Although HVAC manufacturers are investing in new technologies and more efficient products to reduce energy consumption, there is still room for further improvement.

One way of reducing cooling and heating energy in residential buildings is by allowing the centralized HVAC unit to supply conditioned air to only occupied portions of the house by applying smart HVAC zoning. According to the United States Energy Information Administration [3], the percentage of houses equipped with centralized HVAC units is over 70%, which makes this thesis applicable to the majority of houses in the United States. This thesis proposes to implement HVAC zoning in a smart way to eliminate all human errors, such as leaving the AC unit on all day, which turns out to be causing a serious amount of energy to be wasted.

The total amount of energy that could be saved by implementing the concepts presented in this thesis in all single-family houses in the U.S. is estimated to be about 156 billion kWh annually. This amount of energy reduction is proportional to the electricity bills and the amount of dollars paid annually on energy that is technically being wasted.
ContributorsFairag, Amr (Author) / Phelan, Patrick (Thesis advisor) / Bocanegra, Luis (Committee member) / Shuaib, Abdelrahman (Committee member) / Arizona State University (Publisher)
Created2018
157169-Thumbnail Image.png
Description
When air is supplied to a conditioned space, the temperature and humidity of the air often contribute to the comfort and health of the occupants within the space. However, the vapor compression system, which is the standard air conditioning configuration, requires air to reach the dew point for dehumidification to

When air is supplied to a conditioned space, the temperature and humidity of the air often contribute to the comfort and health of the occupants within the space. However, the vapor compression system, which is the standard air conditioning configuration, requires air to reach the dew point for dehumidification to occur, which can decrease system efficiency and longevity in low temperature applications.

To improve performance, some systems dehumidify the air before cooling. One common dehumidifier is the desiccant wheel, in which solid desiccant absorbs moisture out of the air while rotating through circular housing. This system improves performance, especially when the desiccant is regenerated with waste or solar heat; however, the heat of regeneration is very large, as the water absorbed during dehumidification must be evaporated. N-isopropylacrylamide (NIPAAm), a sorbent that oozes water when raised above a certain temperature, could potentially replace traditional desiccants in dehumidifiers. The heat of regeneration for NIPAAm consists of some sensible heat to bring the sorbent to the regeneration temperature, plus some latent heat to offset any liquid water that is evaporated as it is exuded from the NIPAAm. This means the NIPAAm regeneration heat has the potential to be much lower than that of a traditional desiccant.

Models were created for a standard vapor compression air conditioning system, two desiccant systems, and two theoretical NIPAAm systems. All components were modeled for simplified steady state operation. For a moderate percent of water evaporated during regeneration, it was found that the NIPAAm systems perform better than standard vapor compression. When compared to the desiccant systems, the NIPAAm systems performed better at almost all percent evaporation values. The regeneration heat was modeled as if supplied by an electric heater. If a cheaper heat source were utilized, the case for NIPAAm would be even stronger.

Future work on NIPAAm dehumidification should focus on lowering the percent evaporation from the 67% value found in literature. Additionally, the NIPAAm cannot exceed the lower critical solution temperature during dehumidification, indicating that a NIPAAm dehumidification system should be carefully designed such that the sorbent temperature is kept sufficiently low during dehumidification.
ContributorsKocher, Jordan Daniel (Author) / Wang, Robert (Thesis advisor) / Phelan, Patrick (Committee member) / Parrish, Kristen (Committee member) / Arizona State University (Publisher)
Created2019