The need for alternative energy efficient building heating and cooling technologies has given rise to the development and widespread use of Ground Coupled Heat Pump (GCHP) systems. This dissertation looks at the feasibility of using GCHP systems as a viable economic alternative to traditional air source cooling systems (ASHP) for

The need for alternative energy efficient building heating and cooling technologies has given rise to the development and widespread use of Ground Coupled Heat Pump (GCHP) systems. This dissertation looks at the feasibility of using GCHP systems as a viable economic alternative to traditional air source cooling systems (ASHP) for conditioning buildings in the hot, semi-arid climate of Phoenix, Arizona. Despite high initial costs, GCHPs are gaining a foothold in northern climates where heating dominates, in large part due to government incentives. However, due to issues associated with low ground heat exchanger (GHE) efficiency and thermally-induced soil deformations, GCHPs are typically not considered a viable option in hot climates with deep groundwater and low permeability soil. To evaluate the energy performance and technical feasibility of GCHPs in Phoenix, the DOE 5,500 sq.ft small office, commercial building prototype was simulated in EnergyPlus to determine the cooling and heating loads. Next, a commercial software program, Ground Loop Design (GLD), was used to design and simulate the annual energy performance of both vertical (V-GCHPs) and horizontal GCHPs (H-GCHPs). Life cycle costs (LCC) were evaluated using realistic market costs both under dry, as well as fully saturated soil conditions (meant as an upper performance limit achievable by ground modification techniques). This analysis included performing several sensitivity analyses and also investigating the effect of financial rebates. The range of annual energy savings from the GCHP system for space cooling and heating was around 38-40% compared to ASHPs for dry soil. Saturated soil condition significantly affects the length of the GHE. For V-GCHPs, there was about 26% decrease in the length of GHE, thereby reducing the initial cost by 18-19% and decreasing the payback period by 24-25%. Likewise, for H-GCHPs, the length of GHE was reduced by 25% resulting in 22% and 39-42 % reduction in the initial cost and payback period respectively. With federal incentives, H-GCHPs under saturated soil conditions have the least LCC and a good payback periods of 2.3-4.7 years. V-GCHPs systems were been found to have payback periods of over 25 years, making them unfeasible for Phoenix, AZ, for the type of building investigated.
ContributorsTambe, Vaibhavi Parmanand (Author) / Reddy, T Agami (Thesis advisor) / Kavanzanjian, Edward (Thesis advisor) / Bryan, Harvey (Committee member) / Arizona State University (Publisher)
Created2014
150762-Thumbnail Image.png
Description
Building Envelope includes walls, roofs and openings, which react to the outdoor environmental condition. Today, with the increasing use of glass in building envelope, the energy usage of the buildings is increasing, especially in the offices and commercial buildings. Use of right glass type and control triggers helps to optimize

Building Envelope includes walls, roofs and openings, which react to the outdoor environmental condition. Today, with the increasing use of glass in building envelope, the energy usage of the buildings is increasing, especially in the offices and commercial buildings. Use of right glass type and control triggers helps to optimize the energy use, by tradeoff between optical and thermal properties. The part of the research looks at the different control triggers and its range that governs the use of electrochromic glass to regulate the energy usage in building. All different control trigger that can be possibly used for regulating the clear and tint state of glass were analyzed with most appropriate range. Its range was triggered such that 80% time of the glass is trigger between the ranges. The other building parameters like window wall ratio and orientations were also investigated. The other half of the research study looks into the feasibility of using the Electrochromic windows, as it is ought to be the main factor governing the market usage of Electrochromic windows and to investigate the possible ways to make it feasible. Different LCC parameters were studied to make it market feasible product. This study shows that installing this technology with most appropriate trigger range can reduce annual building energy consumption from 6-8% but still cost of the technology is 3 times the ASHRAE glass, which results in 70-90 years of payback. This study concludes that south orientation saves up to 3-5% of energy and 4-6% of cooling tons while north orientation gives negligible saving using EC glass. LCC parameters show that there is relative change in increasing the net saving for different parameters but none except 50% of the present glass cost is the possible option where significant change is observed.
ContributorsMunshi, Kavish Prakash (Author) / Bryan, Harvey (Thesis advisor) / Reddy, Agami (Committee member) / Addison, Marlin (Committee member) / Arizona State University (Publisher)
Created2012
149515-Thumbnail Image.png
Description
With the increasing interest in energy efficient building design, whole building energy simulation programs are increasingly employed in the design process to help architects and engineers determine which design alternatives save energy and are cost effective. DOE-2 is one of the most popular programs used by the building energy simulation

With the increasing interest in energy efficient building design, whole building energy simulation programs are increasingly employed in the design process to help architects and engineers determine which design alternatives save energy and are cost effective. DOE-2 is one of the most popular programs used by the building energy simulation community. eQUEST is a powerful graphic user interface for the DOE-2 engine. EnergyPlus is the newest generation simulation program under development by the U.S. Department of Energy which adds new modeling features beyond the DOE-2's capability. The new modeling capabilities of EnergyPlus make it possible to model new and complex building technologies which cannot be modeled by other whole building energy simulation programs. On the other hand, EnergyPlus models, especially with a large number of zones, run much slower than those of eQUEST. Both eQUEST and EnergyPlus offer their own set of advantages and disadvantages. The choice of which building simulation program should be used might vary in each case. The purpose of this thesis is to investigate the potential of both the programs to do the whole building energy analysis and compare the results with the actual building energy performance. For this purpose the energy simulation of a fully functional building is done in eQUEST and EnergyPlus and the results were compared with utility data of the building to identify the degree of closeness with which simulation results match with the actual heat and energy flows in building. It was observed in this study that eQUEST is easy to use and quick in producing results that would especially help in the taking critical decisions during the design phase. On the other hand EnergyPlus aids in modeling complex systems, producing more accurate results, but consumes more time. The choice of simulation program might change depending on the usability and applicability of the program to our need in different phases of a building's lifecycle. Therefore, it makes sense if a common front end is designed for both these simulation programs thereby allowing the user to select either the DOE-2.2 engine or the EnergyPlus engine based upon the need in each particular case.
ContributorsRallapalli, Hema Sree (Author) / Bryan, Harvey (Thesis advisor) / Addison, Marlin (Committee member) / Reddy, Agami (Committee member) / Arizona State University (Publisher)
Created2010
153551-Thumbnail Image.png
Description
An acute and crucial societal problem is the energy consumed in existing commercial buildings. There are 1.5 million commercial buildings in the U.S. with only about 3% being built each year. Hence, existing buildings need to be properly operated and maintained for several decades. Application of integrated centralized control systems

An acute and crucial societal problem is the energy consumed in existing commercial buildings. There are 1.5 million commercial buildings in the U.S. with only about 3% being built each year. Hence, existing buildings need to be properly operated and maintained for several decades. Application of integrated centralized control systems in buildings could lead to more than 50% energy savings.

This research work demonstrates an innovative adaptive integrated lighting control approach which could achieve significant energy savings and increase indoor comfort in high performance office buildings. In the first phase of the study, a predictive algorithm was developed and validated through experiments in an actual test room. The objective was to regulate daylight on a specified work plane by controlling the blind slat angles. Furthermore, a sensor-based integrated adaptive lighting controller was designed in Simulink which included an innovative sensor optimization approach based on genetic algorithm to minimize the number of sensors and efficiently place them in the office. The controller was designed based on simple integral controllers. The objective of developed control algorithm was to improve the illuminance situation in the office through controlling the daylight and electrical lighting. To evaluate the performance of the system, the controller was applied on experimental office model in Lee et al.’s research study in 1998. The result of the developed control approach indicate a significantly improvement in lighting situation and 1-23% and 50-78% monthly electrical energy savings in the office model, compared to two static strategies when the blinds were left open and closed during the whole year respectively.
ContributorsKarizi, Nasim (Author) / Reddy, T. Agami (Thesis advisor) / Bryan, Harvey (Committee member) / Dasgupta, Partha (Committee member) / Kroelinger, Michael D. (Committee member) / Arizona State University (Publisher)
Created2015