Increasing computational demands in data centers require facilities to operate at higher ambient temperatures and at higher power densities. Conventionally, data centers are cooled with electrically-driven vapor-compressor equipment. This paper proposes an alternative data center cooling architecture that is heat-driven. The source is heat produced by the computer equipment. This

Increasing computational demands in data centers require facilities to operate at higher ambient temperatures and at higher power densities. Conventionally, data centers are cooled with electrically-driven vapor-compressor equipment. This paper proposes an alternative data center cooling architecture that is heat-driven. The source is heat produced by the computer equipment. This dissertation details experiments investigating the quantity and quality of heat that can be captured from a liquid-cooled microprocessor on a computer server blade from a data center. The experiments involve four liquid-cooling setups and associated heat-extraction, including a radical approach using mineral oil. The trials examine the feasibility of using the thermal energy from a CPU to drive a cooling process. Uniquely, the investigation establishes an interesting and useful relationship simultaneously among CPU temperatures, power, and utilization levels. In response to the system data, this project explores the heat, temperature and power effects of adding insulation, varying water flow, CPU loading, and varying the cold plate-to-CPU clamping pressure. The idea is to provide an optimal and steady range of temperatures necessary for a chiller to operate. Results indicate an increasing relationship among CPU temperature, power and utilization. Since the dissipated heat can be captured and removed from the system for reuse elsewhere, the need for electricity-consuming computer fans is eliminated. Thermocouple readings of CPU temperatures as high as 93°C and a calculated CPU thermal energy up to 67Wth show a sufficiently high temperature and thermal energy to serve as the input temperature and heat medium input to an absorption chiller. This dissertation performs a detailed analysis of the exergy of a processor and determines the maximum amount of energy utilizable for work. Exergy as a source of realizable work is separated into its two contributing constituents: thermal exergy and informational exergy. The informational exergy is that usable form of work contained within the most fundamental unit of information output by a switching device within a CPU. Exergetic thermal, informational and efficiency values are calculated and plotted for our particular CPU, showing how the datasheet standards compare with experimental values. The dissertation concludes with a discussion of the work's significance.
ContributorsHaywood, Anna (Author) / Phelan, Patrick E (Thesis advisor) / Herrmann, Marcus (Committee member) / Gupta, Sandeep (Committee member) / Trimble, Steve (Committee member) / Myhajlenko, Stefan (Committee member) / Arizona State University (Publisher)
Created2014
153410-Thumbnail Image.png
Description
With the ever-increasing demand for high-end services, technological companies have been forced to operate on high performance servers. In addition to the customer services, the company's internal need to store and manage huge amounts of data has also increased their need to invest in High Density Data Centers. As a

With the ever-increasing demand for high-end services, technological companies have been forced to operate on high performance servers. In addition to the customer services, the company's internal need to store and manage huge amounts of data has also increased their need to invest in High Density Data Centers. As a result, the performance to size of the data center has increased tremendously. Most of the consumed power by the servers is emitted as heat. In a High Density Data Center, the power per floor space area is higher compared to the regular data center. Hence the thermal management of this type of data center is relatively complicated.

Because of the very high power emission in a smaller containment, improper maintenance can result in failure of the data center operation in a shorter period. Hence the response time of the cooler to the temperature rise of the servers is very critical. Any delay in response will constantly lead to increased temperature and hence the server's failure.

In this paper, the significance of this delay time is understood by performing CFD simulation on different variants of High Density Modules using ANSYS Fluent. It was found out that the delay was becoming longer as the size of the data center increases. But the overload temperature, ie. the temperature rise beyond the set-point became lower with the increase in data center size. The results were common for both the single-row and the double-row model. The causes of the increased delay are accounted and explained in detail manner in this paper.
ContributorsRamaraj, Dinesh Balaji (Author) / Gupta, Sandeep (Thesis advisor) / Hermann, Marcus (Committee member) / Huang, Huei-Ping (Committee member) / Arizona State University (Publisher)
Created2015
135148-Thumbnail Image.png
Description
\English is a programming language, a method of allowing programmers to write instructions such that a computer may understand and execute said instructions in the form of a program. Though many programming languages exist, this particular language is designed for ease of development and heavy optimizability in ways that no

\English is a programming language, a method of allowing programmers to write instructions such that a computer may understand and execute said instructions in the form of a program. Though many programming languages exist, this particular language is designed for ease of development and heavy optimizability in ways that no other programming language is. Building on the principles of Assembly level efficiency, referential integrity, and high order functionality, this language is able to produce extremely efficient code; meanwhile, programmatically defined English-based reusable syntax and a strong, static type system make \English easier to read and write than many existing programming languages. Its generalization of all language structures and components to operators leaves the language syntax open to project-specific syntactical structuring, making it more easily applicable in more cases. The thesis project requirements came in three parts: a compiler to compile \English code into NASM Assembly to produce a final program product; a standard library to define many of the basic operations of the language, including the creation of lists; and C translation library that would utilize \English properties to compile C code using the \English compiler. Though designed and partially coded, the compiler remains incomplete. The standard library, C translation library, and design of the language were completed. Additional tools regarding the language design and implementation were also created, including a Gedit syntax highlighting configuration file; usage documentation describing in a tutorial style the basic usage of the language; and more. Though the thesis project itself may be complete, the \English project will continue in order to produce a new language capable of the abilities possible with the design of this language.